Également pour Danfoss VLT HVAC Drive FC 102 : Manuel d'utilisation (16 pages), Manuel d'installation (20 pages), Manuel d'instructions d'installation (6 pages), Manuel d'instructions d'installation (12 pages), Manuel d'installation (18 pages), Manuel d'instructions d'installation (8 pages), Manuel d'instructions d'installation (10 pages), Manuel d'installation (6 pages), Manuel d'utilisation (16 pages), Manuel d'instructions d'installation (6 pages), Manuel d'installation (16 pages), Manuel d'installation (8 pages), Manuel d'instruction (16 pages), Manuel d'instructions d'installation (6 pages), Manuel d'installation (6 pages)

Danfoss VLT HVAC Drive FC 102 Manuel d'instructions d'installation
Installation Instructions

Application Integration

PTU 025 is designed for central air handling units with 1 or more filters in the inlet/outlet part and with fan control based on the
airflow or pressure level in the ventilation system. Separate frequency converters with separate pressure transmitter units control
the inlet and outlet. PTU 025 has 4 pressure inputs. See the pressure ranges in Table 1.4. Sensors 3 and 4 can be configured for
either filter monitoring or PID control of the airflow or the pressure level.
Illustration 1.10 Application Integration Example
#
Range
1
0–500 Pa
2
0–500 Pa
3
0–1000 Pa
4
0–2500 Pa
Table 1.4 PTU 025 Sensors and their Functions
Integrating pressure signals into a system solution
The pressure values can be read as analog values on the
analog output or as pulses on digital outputs. Use
parameter 5-30 Terminal 27 Digital Output,
parameter 5-31 Terminal 29 Digital Output, and
parameter 5-40 Function Relay to send the sensor status to the
relay or digital outputs. For more information about using the
pressure values in applications and in the smart logic control,
see the programming guide.
MI08A102
Pressure Transmitter Unit PTU 025
®
VLT
HVAC Drive FC 102
Typical function
Filter monitoring
Filter monitoring
Filter monitoring or PID control of the airflow or the pressure level
Filter monitoring or PID control of the airflow or the pressure level
PID closed-loop control based on the airflow or pressure
level
Use parameters in parameter group 20-0* Feedback to use the
pressure values for the frequency converter's closed-loop PID
controller.
Use parameters in parameter group 22-** Application Functions
to configure the monitoring of HVAC applications based on
airflow. For more information, see the operating guide and the
programming guide.