Electrical Installation
If the CO200 Duct is to be used to monitor possible leakage of carbon monoxide in boiler rooms due to
spillage or damaged or unsuitable flue systems, it is advisable to connect the sensor directly to a Duomo gas
control panel. These are safety devices and are designed to give audible alarms and automatically provide
latched electrical isolation of associated gas safety shut off valves.
The CO200 Duct is also suitable for carbon monoxide sensing in car parks and can be connected either to
Duomo gas control panels or to Building Management Systems (BMS). The sensor can be located up to 100m
from the gas detector. Cable size should be 1mm csa. If the sensor cables are run seperately in specific conduit
it is not essential to use screened cable.
However, if the cables are routed through conduit or trunking containing other wiring the use of screened
cable is advisable. The wiring should be performed by a qualified person in accordance with current
regulations.The plug in terminal rail makes installation easy and quick.
Commissioning
It is strongly recommended that this sensor should be commissioned by Duomo Commissioning Engineers or engineers
approved by Duomo to carry out this work. A quotation for commissioning or service will be provided upon request.
Contact our service department by;
Telephone - 01905 797989
Fax - 01905 774296
Email - [email protected]
The benefits of this equipment being commissioned by Duomo are:
The 3 year guarantee period will start from the date of commissioning and not from the date of manufacture
On board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will carry spares
to ensure that the commissioning is successful
A Duomo Commissioning Certificate is provided
It is prudent to make electrical connection to the sensor terminal plug when withdrawn and leave the plug
disconnected from the sensor so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to
be checked prior to commissioning and avoids damage due to incorrect connection. Guarantees for this product will
become void if damage is caused by the installer.
Technical Specifications
Power supply
Electrical input
External protection rating
Working temperature
Sensor type
Detection precision
CE certification
Detection
Response time
Interconnecting cable size
Material used for housing
Dimensions
Function check period
Guarantee
12-24V DC +/- 10% from detector
110mA @ 13.8V
IP55
o
o
-10
C to 40
C
Electrochemical
1% full scale
No. 96125
0 to 300ppm
< 10 seconds
1mm csa
Aluminium
75 x 158 x 58
6 months
3 years