LOAD UNBALANCE
To enable the load unbalance function and configure the maximum current
phase unbalance according to local regulations. This configuration is mandatory
in the following countries:
•
Germany
•
Austria
•
Switzerland
•
Netherlands
The functionality is off by default. To activate it, click on the drop down menu and
select the current value according to the maximum allowable current unbalance
between the phases.
This value is 20A for Germany and 16A for Austria, Switzerland and Netherlands.
Once the functionality is enabled, to make the changes effective, always restart
the wallbox through the dedicated button in the hompage.
Installation manual - Annex