DUOTEC AHV200024 Manuel d'utilisation et d'installation - Page 10
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation et d'installation pour {nom_de_la_catégorie} DUOTEC AHV200024. DUOTEC AHV200024 16 pages.
OWNER'S MANUAL INSTALLATION INSTRUCTIONS
BLOWER MOTOR - CFM
FAN CONTROL BOARD CONFIGURATION
The Fan Control Board can be configured by the installer and should
be operated within its specified CFM range (refer to Table 2). The
ECM motor uses wire selection taps (A through F) to modify
operation determined from a pre-programmed airflow table (refer to
Figure 6 for wire selection and tap identification, and Tables 4 and
7 for airflows). Airflows are based on system size and/or mode of
operation. These airflows are automatically modified as needed in
response to other inputs such as the need for dehumidification, etc.
Table 2
AHV Modular CFM (L/s) Range
Unit Size
Outdoor Unit
Size
AHV08
18
24
30
36
AHV12
24
30
36
42
AHV16
36
42
48
60
AHV20
36
42
48
60
The AHV unit must be configured to operate properly with all of the
system components that have been installed. To successfully
configure a basic system, move the wire selection tap (as needed) to
the proper pin position.
NOTE: The factory default setting for all selections is the first pin. It
is recommended the installer review each setting (see below and
refer to Figure 6 for wire selection and tap identification).
A. AUXILIARY HEAT KW/CFM (VIOLET WIRE)
Select the CFM range based on the electric heater kW size by using
the Violet wire.
If no heater is installed, this step can be skipped. However, when an
electric heater is applied, move the Violet wire to the proper A, B, C,
D pin selection. Refer to Table 8 for heater range selection. The
heater kW ranges corresponds directly to each pin letter listed in the
table.
The airflow must be greater than the minimum CFM for electric heater
application with the size system installed for safe and continuous
operation. (refer to Tables 4 and 5 for airflow).
NOTE: Airflow marked is the airflow which will be supplied in
emergency heat mode and heating mode on air conditioners when
electric heat is the primary heating source.
In heat pump heating mode when electric heaters are energized, the
ECM motor will run the higher or heat pump heating airflow and
electric heater airflow to ensure safe heater operation. The factory
selection is the largest heater range approved.
CFM
L/s
350 - 1200
165-566
415 - 1600
196-755
540 - 2000
255-944
540 - 2000
255-944
8
B. OUTDOOR UNIT SIZE (BLUE WIRE)
Select the outdoor unit system size (BTU) by using the Blue wire
(refer to Table 9).The installer needs to properly select the outdoor
unit size to ensure proper airflow delivery of the modular unit. This
selection affects all operational modes (airflow) with the exception
of electric heat modes.
Move the Blue wire to the proper A, B, C, D pin selection. The outdoor
unit size corresponding directly to each pin letter is listed in Table 7.
C. SYSTEM TYPE - AC/HP (ORANGE WIRE)
Select the system type (AC, HP-Comfort, HP-Efficiency) by using the
Orange wire.
•
AC - Air Conditioner selection provides approximately 400 CFM
per ton for greater efficiency and humidity control with the AC/HP
CFM ADJUST set to the nominal (NOM) tap. (To achieve
approximately 460 CFM per ton move tap to (HI) position. Refer
to appropriate airflow tables for exact CFM setting.)
•
HP-COMFORT - Heat Pump Comfort selection provides
approximately 350 CFM per ton for higher than normal heating
air delivery temperature. Provides approximately 350 CFM per
ton cooling airflow for good humidity removal with the AC/HP
CFM ADJUST set to the nominal (NOM) tap.
•
HP-EFF - Heat Pump Efficiency selection provides same airflow
for heating and cooling modes to increase overall HP efficiency;
approximately 400 CFM per ton with the AC/HP CFM ADJUST
set to the nominal (NOM) tap.
D. AC/HP CFM ADJUST
Select the system AC/HP CFM Adjust by using the Black wire. This
selection basically selects; Medium, Low, or High Airflow
•
NOM - provides airflow at rates described above, the AC/HP
ADJUST select is factory set to the nominal (NOM) tap. The
adjust selections HI/LO will regulate airflow supplied for all
operational modes, except non-heat pump heating modes.
•
HI - provides 15% airflow over nominal unit size selected
•
LO - provides 10% airflow below nominal unit size selected.
Adjust selection options are provided to adjust airflow supplied to
meet individual installation needs for such things as noise, comfort,
and humidity removal.
E. ON/OFF DELAY
Select the ON/OFF delay by using the White wire. This selection
basically selects the desired time delay profile.
NOTE: Delay selections are active in cooling and heat pump heating
modes only. Auxiliary heating modes have a one (1) minute off delay
and zero (0) on delay programmed into the ECM motor that cannot
be overridden.
Choose one (1) of four (4) motor operation delays to customize and
enhance system operation as follows.
Selection options are:
1. 0/90: 0 (zero) second on-delay and 90 second off-delay at 100%
airflow (factory setting).
2. 30/90: 30 second on-delay with no airflow and 90 second off-
delay at 100% airflow profile. Used when it is desirable to allow
system coils time to heat-up/cool-down in conjunction with the
airflow.
3.
0/0: 0 (zero) second on-delay option and 0 (zero) second off-
delay. Used for servicing unit or when a thermostat is utilized to
perform delay functions.
4. ENH: Enhanced selection provides a 30 second on-delay with no
airflow followed by 150 seconds at 70% airflow, and 0(zero)
second off-delay for added comfort. This profile will minimize cold
blow in heat pump operation and could enhance system
efficiency.
DUOTEC AIR HANDLER: AHV