DANLERS CESRAPIRSD Notes d'installation

Parcourez en ligne ou téléchargez le pdf Notes d'installation pour {nom_de_la_catégorie} DANLERS CESRAPIRSD. DANLERS CESRAPIRSD 2 pages. Ceiling surface pir absence switch/dim control (round)

DANLERS CESRAPIRSD Notes d'installation
Troubleshooting
The load will not switch on:
• The LUX adjuster is set too low and is inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• Please contact DANLERS for further technical support.
Momentary switches
DANLERS can supply a range of Momentary/Retractive switches -
push to make or break:
MOMSW MP - Plated grey metal finish with PRESS preprinted on switch.
MOMSW M - Plated grey metal finish with blank switch.
MOMSW WHP - Plated white finish with PRESS preprinted on switch
MOMSW WH - Plated white finish with blank switch.
MOMSW PMOD - Grid module suitable for MK Grid Plus with PRESS
preprinted on switch.
MOMSW MOD - Grid module suitable for MK Grid Plus with blank switch.
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
15/12/15
INS231 CESRAPIRSD
Ceiling surface PIR absence switch/dim control (round)
CESRAPIRSD
DANLERS ceiling surface passive infra-red absence switch/dim controls
(CESRAPIRSD) can be mounted directly onto solid ceilings or onto a
range of different mounting boxes.
CESRAPIRSD controls incorporate a passive infra-red quad sensor to
detect movement of a warm body within their detection zone (diagram
A) and a photocell to monitor the ambient light level.
When entering the room, if the ambient light is dark enough, the lights can
be activated by using a momentary light switch. The ambient threshold
can be set by the user to between approximately 30 lux and 1000 lux
and maximum (photocell inactive) at the PIR via the LUX adjuster
(diagram B). If no more movement is detected within a pre-selected
time, then the CESRAPIRSD will switch the load off. This time lag can
be set via the TIME adjuster to 10 seconds, 20s, 40s, 80 s, 2m 30s, 5m,
10m, 20m or 40 minutes (diagram B).
Pressing the momentary switch again (while CESRAPIRSD is in its
ON state) will operate the SWITCH AND DIM function of the ballast.
Please refer to ballast manufacturer's data sheets for operation and
synchronisation of the ballast.
Loading
CESRAPIRSD can switch up to:
6 amps (1500W) of resistive loads.
6 amps (1500W) of fluorescent loads.
3 amps (750W) of electronic and wire wound transformer loads.
2 amps (500W) of CFL, 2D lamps, LED Drivers and LED lamps
and fittings.
1 amp (250W) of fans.
Minimum load 2W resistive, suitable for most energy saving lamps,
LEDs and emergency fittings.

Installation notes