Compact Person Detection Switches
Input: 220-240 Vac 50Hz
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT
DANLERS COPIR IP66(BK) is IP66 rated and
can be surface mounted onto an external wall.
It incorporates a passive infra-red sensor to
detect movement of a warm body within the
detection zone (diagram 1) and it includes a
photocell to monitor the ambient light level.
The detection range is about 10 metres over
120 degrees, the range reduces to about 8m
at the extremes to prevent nuisance switching.
Product codes:
COPIR IP66: White enclosure (Grey front
facet).
COPIR IP66 BK: Black enclosure.
INSTALLATION PROCEDURE
1. Please read these notes carefully before
commencing work. In case of doubt please
consult a qualifi ed electrician.
2. The detector should be sited so that it is not
shaded from daylight
3. The detector should be mounted between
1 and 2.2 metres high, via any of the four
pre-drilled mounting holes only.
4. It must be mounted with the cable entering
from below.
5. Make sure the power is isolated from the
circuit.
6. The detector should be connected as
shown in diagram overleaf.
L - Live in, N - Neutral in,
SL - Switched Line out.
7. IMPORTANT - Replace terminal cover.
8. Once the wiring has been completed and
verifi ed, switch on the supply and test the
operation.
START UP MODE
When the PIR is powered up, the PIR will
switch on the lighting load for 1 minute then
switch it off. After 2 seconds it will switch
on again if it detects movement. With Time
set to minimum the load will stay on for 10
seconds so the detection range can be
easily assessed. If a manual override-off
switch after the PIR (diagrams 5 & 6, note 1)
it will not enter the start-up mode each time.
LOADING: See overleaf
LUX AND TIME SET UP
On detecting movement, if the ambient light is
dark enough, the COPIR IP66 (BK) will switch
the load on. The ambient threshold can be set
by the user to between approximately 10 and
1000 lux via the internal LUX adjuster (diagrams
2 and 3). The photocell can be disabled via the
internal mode button (see overleaf).
If no more movement is detected within a
pre-selected time, then the PIR switch will
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388 E-mail: [email protected]
www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
DAT0027 COPIR IP66
turn the load off. This time lag can be set via
the TIME adjuster to 10 seconds, 20 seconds,
40 seconds, 80 seconds, 2 minutes 30
seconds, 5 minutes,10 minutes, 20 minutes
or 40 minutes (diagram 4).
For convenience, ensure that the TIME is set to
minimum when setting up the LUX level. Afterwards
set the TIME to a value suitable for the application.
1. When powered up, (after 1 minute
stabilisation time) turn lux pot (diagram
C) fully clockwise and time pot fully
anticlockwise.
2. Press the MODE button (diagram 2) for
approximately 0.5s. The LED will go green
indicating the LUX cell is active. (Or press
and hold button for approx. 4 seconds – LED
goes RED indicating Lux cell INACTIVE).
Repeating these steps will toggle the
functionality.
3. If lux cell active, vacate area until PIR switch
switches the load off (should be after 10
seconds).
4. With the LUX as desired on working plane
from daylight ONLY (no artifi cial light), wind
the lux pot anticlockwise whilst waving your
hand in front of the PIR cell. When the PIR
switches the load ON, stop turning the pot.
The Lux inhibit level is now set.
5. Turn the PIR time to the desired timeout
(diagram 4). Whenever a person is detected,
the time lag will start again and the load will
stay switched on.
TROUBLESHOOTING
The PIR does not detect:
• Check power supply.
• Is there an obstruction in front of the lens?
• Person is too far from the COPIR IP66
switch, see detection diagram.
• Person is moving unusually slowly (perhaps
when testing).
• To perform detection test - turn the time
spindle to minimum setting (10 seconds),
cover the lens to stop any detection - load
should switch off in 10 seconds unless going
through its START UP MODE (see opposite).
The PIR stops working
• Ensure the unit is mounted correctly so that
no water can enter.
The PIR false triggers
• Detector is exposed to air movement on
breezy days.
DIAGRAM 1 - WALL MOUNTED DETECTION
Dual colour LED:
RED - PIR active,
Photocell inactive
GREEN - PIR and
Photocell override ON
(passive LUX)
Time
Delay
Spindle
DIAGRAM 2 - TIME / LUX ADJUSTERS (INSIDE CASING)
2.5m
80s
5m
Use Mode
40s
10m
Button to
20s
20m
disable LUX
(see diagram
10s
40m
2)
min
max
TIME
DIAGRAM 3 - LUX ADJUSTMENT
Inside
detector
housing
DIAGRAM 4 - ADJUSTING TIME LAG
Terminal cover
(safety cap)
Locate safety cap plastic
pins in the hole 'L' and
second 'N' holes above
the termination screws.
Press firmly to attach.
DIAGRAM 5 - TERMINAL COVER
Recommended mounting
height 1 to 2.2 metres
Strong detection zone (5m)
i.e. person walking
towards detector
Secondary
detection zone
(10m, 8m at
extremes)
i.e. person walking
perpendicular to
detector
Lux Cell
Mode
STATUS
MODE
Lux
Setting
1000
10
Spindle
TIME
LUX
1000 LUX
10 LUX
max
min
LUX
2.5m
80s
5m
40s
10m
20s
20m
10s
40m
min
max
TIME