DANLERS MWCEFL Notes d'installation - Page 2

Parcourez en ligne ou téléchargez le pdf Notes d'installation pour {nom_de_la_catégorie} DANLERS MWCEFL. DANLERS MWCEFL 2 pages. Ceiling flush mounted microwave presence detector switch

Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. Make sure the power is isolated from the circuit.
3. TO ACCESS THE TERMINALS: Remove the safety cap enclosure lid by pressing
the two release clips under the spring coils with a small flat head screwdriver.
Carefully remove the enclosure.
4. Once wiring is securely connected to the terminals and the cable(s) secured to the
cable clips replace the safety cap with the open face on the opposite side to the
terminals for safety.
5. For fully automatic mode the MWCEFL should be connected as shown in
diagram D:
L (Live in). N (Neutral in). SL(Switched Line out).
6. If the override function is required the MWCEFL should be connected using the
'PUSH' terminal as shown in diagram E:
L (Live in). N (Neutral in). SL(Switched Line out). PUSH (to retractive wall switch)
Settings
Detection range, Hold time (time lag) and Daylight sensor threshold can be set via
the settings spindle (see diagram A) behind the lens cap on the front face of the
MWCEFL (see diagram B).
To remove the lens cap: Make sure the power is isolated from the circuit.
Place a fine pointed instrument in the small hole under the 'Open' icon. Gently push
the cap away from the main body. The spindle can be rotated with a small flat head
screwdriver.
Channel
Detection
Hold time
Photocell
range
0
100%
5 seconds
Disable
1
100%
30 seconds
2 lux
2
100%
1 minute
10 lux
3
100%
5 minute
2 lux
4
100%
5 minute
10 lux
5
100%
5 minute
30 lux
6
100%
5 minute
50 lux
7
100%
5 minute
Disable
8
100%
10 minute
10 lux
9
100%
10 minute
30 lux
A
100%
10 minute
50 lux
B
75%
10 minute
30 lux
C
50%
10 minute
10 lux
D
100%
30 minute
10 lux
E
100%
30 minute
50 lux
F
100%
5 seconds
2 lux
A: Settings Spindle
A
B: Installation
Release
Clip
Release
Clip
Terminals
Photocell
Lens
Settings
Cap
Spindle
C: Detection diagram
Ceiling mounting detection pattern (m)
6
5
4
3
2
1
0
1
1
2
3
4
5
6
D: Wiring diagram
N
220-240VAC 50/60Hz
L
N
Control gear
L
N
Control gear
L
PUSH
L'
N
N
L
Requires 70mm
diameter hole
in a false or
plasterboard ceiling
2
3
4
5
6
100% Detection Pattern
75% Detection Pattern
50% Detection Pattern
E: Wiring diagram
N
220-240VAC 50/60Hz
L
Push Switch
to override
ON or OFF
N
Control gear
L
N
Control gear
L
PUSH
L'
N
N
L