Follow the manufacturer's recommended instructions for curing the oven. Failure to follow the curing
schedule can cause damage to the oven, and void the oven warranty.

1. MINIMUM INSTALLATION CLEARANCES

The oven shall be installed a minimum of 1" away from combustible material from back and side walls to
oven and 14" above the oven. In addition, there must be clearance of minimum 30" from combustible
material adjacent to the sides of the oven opening. If the distance is less than 30 inches a wall shield
must be mounted on the wall. Any adjacent combustible floor which projects in front of the oven opening
must be a minimum of 36" from the front of the door opening. (Figure1)
WARNING: Do not place any type of insulation in the required clearance spaces surrounding the oven.
NOTE: FOR HEALTH DEPARTMENT REQUIREMENTS ANY 1-INCH AIR GAP ADJACENT TO A
COMBUSTIBLE WALL MUST BE SEALED WITH A NON COMBUSTIBLE STRIP. i.e. ALUMINUM,
STAINLESS STEEL OR TILE.