Operation principal
The dehumidifier works with two air flows. The volume of the dehumidified air is bigger. The air
flow of a smaller volume is used for moisture removal from the dehumidifier rotor. The rotor is
subject to the action of different oppositely directed air flows by sectors. The air flow to be
dehumidified (PROCESS AIR) passes through the biggest sector. The moisture from the air is
trapped (adsorbed) by the rotor material. The air leaves the rotor in dehumidified condition (DRY
AIR) and is directed to a certain part of the building or a technological process where
dehumidified air or a certain air humidity levels are required. Since the rotor rotates slowly the
incoming air always contacts with the rotor active part, thus a continuous dehumidification
process is assured.
The air flow used for the rotor matrix regeneration is called regeneration air (REGENERATION
AIR). It is heated up to 120 С and when passing through a small sector it removes the moisture
trapped by the rotor material. The moisture is removed from the rotor in the form of humid air
(MOIST AIR) which is discharged outside the dehumidified loop.
Process air
Process air fan
Filter
Moist air
·
The air to be dehumidified passes through the rotor. Water molecules are absorbed by the rotor.
·
The rotor is reactivated by another air flow preheated to 120 C. The moisture is removed from the room
in the form of moist air.

Dimensions and weight

Insignificant design changes are possible!
Length
Depth
442mm
296mm
о
Adsorption rotor
Rotor motor
Pic.1. Dehumidifier air flows diagram
Dehumidified
Height
air
ø 100 mm
652mm
Dry air
Regeneration air fan
Heater
о
Reactivation
Dry air
air
ø 80 mm
ø 100 mm
5
R
Filter
Regeneration air
Table 1
Moist air
Weight
30 kg
ø 80 mm
www.danvex.fi