Water quality requirements:
Dimensions of the solid particles should not exceed 100 micron and Demineralized water
(demineralization no more than 5 mg on liter). If the water quality does not meet the
mentioned requirements the humidifier must be equipped with a water demineralization
device.
Attention! Never refill water through steam pipes! It will cause the humidifier failure.
It is not allowed to use the device without grounding. Grounding cable section should be
20% larger than the section of power wires.
Commissioning
Prior to commissioning it is necessary to make oneself aware of operating conditions and to
observe them during operation:
Operation
temperature
Range of
humidification
Water quality
requirements
Prior to the first start-up it is necessary to open service panels and to make sure that
there are no foreign objects. It is also necessary to make sure that filters are installed, power
and water supply lines are properly connected to the humidifier. After inspection the service
panels should be closed. It is prohibited to operate the humidifier with open panels.
The humidifier is started by selection of an operating mode with a 3-position switch
located on the right side panel. Before the operating mode selection it is necessary to open
the water supply and to wait till the humidifier tank is filled with water.
The humidifier has two operating modes: manual (MAN) and automatic (AUTO). In
manual mode (MAN) humidification is continuous. In automatic mode (AUTO) humidification
is performed until a humidity set-point is reached. Humidity level is controlled by means of a
remote humidity sensor. The humidity sensor connector is near mode selector switch.
Humidifier automatic operation is impossible without the humidity sensor.
Humidity parameters are monitored and controlled by a controller located on the
humidifier front panel.
Buttons of the humidity controller:
- used for entering the parameters menu;
- used for humidity level increase;
- used for humidity level decrease.
+5..+40℃
10 - 98%
Clean main water (with softener)
Humidity controller indicators:
RUN indicates that the humidifier is running;
upper PV figures display current humidity values;
lower SV figures display the set humidity.
Water
pressure
Water
temperature
Do not place near IR heaters;
Environment
7
1 - 4 bar
+1..+30℃
D o not place near strong
magnetic field sources;
Use in premises with
low dust content
www.danvex.fi