2.2 – Jellyfish Membrane Filtration Cartridge Assembly
The Jellyfish Filter utilizes multiple membrane filtration cartridges. Each cartridge consists of removable cylindrical filtration
"tentacles" attached to a cartridge head plate. Each filtration tentacle has a threaded pipe nipple and o-ring. To attach,
insert the top pipe nipples with the o-ring through the head plate holes and secure with locking nuts. Hex nuts to be hand
tightened and checked with a wrench as shown below.
2.3 – Jellyfish Membrane Filtration Cartridge Installation
Cartridge installation will be performed by trained individuals
and coordinated with the installing site Contractor. Flow
diversion devices are required to be in place until the site is
stabilized (final paving and landscaping in place). Failure to
address this step completely will reduce the time between
required maintenance.
Descend to the cartridge deck (see Safety Notice and
page 3).
Refer to Contech's submittal drawings to determine proper
quantity and placement of Hi-Flo, Draindown and Blank
cartridges with appropriate lids. Lower the Jellyfish membrane
filtration cartridges into the cartridge receptacles within the
cartridge deck. It is possible that not all cartridge receptacles
will be filled with a filter cartridge. In that case, a blank
headplate and blank cartridge lid (no orifice) would be
installed.
Do not force the tentacles down into the cartridge receptacle, as this may damage the membranes. Apply downward
pressure on the cartridge head plate to seat the lubricated rim gasket (thick circular gasket surrounding the circumference
of the head plate) into the cartridge receptacle. (See Figure 3 for details on approved lubricants for use with rim gasket.)
Examine the cartridge lids to differentiate lids with a small orifice, a large orifice, and no orifice.
Lids with a small orifice are to be inserted into the Draindown cartridge receptacles, outside of the backwash
pool weir.
Lids with a large orifice are to be inserted into the Hi-Flo cartridge receptacles within the backwash pool weir.
Lids with no orifice (blank cartridge lids) and a blank headplate are to be inserted into unoccupied cartridge
receptacles.
To install a cartridge lid, align both cartridge lid male threads with the cartridge receptacle female threads before
rotating approximately 1/3 of a full rotation until fimrly seated. Use of an approved rim gasket lubricant may faciliate
installation.
Cartridge Assembly
Jellyfish
Filter Owner's Manual
®
7