Aplisens SGE-25.Modbus Manuel de l'utilisateur - Page 10
Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} Aplisens SGE-25.Modbus. Aplisens SGE-25.Modbus 20 pages. Smart level probes
EN.IO.SGE.25.MODBUS
7.
ELECTRICAL CONNECTION
7.1. Connection, signal output
All connection and assembly activities must be performed with the power supply
disconnected and other external voltages, if used.
Incorrect connection of the probe may endanger safety.
Risk of electric shock and / or ignition in hazardous areas.
The electrical connection should be made according to Table. 2. It is recommended to install
the PP-Modbus connection box manufactured by Aplisens S.A. to connect the probe cable with the rest
of the transmission line. The PP-Modbus junction box is non-hermetic (pressure inside is equal to
atmospheric pressure) due to the use of an air filter, which is required for the probe to operate correctly.
Do not allow the capillary outlet to become contaminated or any liquid to enter the capillary.
Table 2. Probe connection.
7.2. Power supply
7.2.1. Power supply voltage
Supply cables may be live.
There is a risk of electric shock and/or explosion.
Installation in potentially explosive atmospheres must comply with local standards
and regulations.
Table 3. Permissible power supply voltage for probes.
Mode
MODBUS mode - standard
version*
MODBUS mode Exi version
Configuration mode – standard
version
*- power consumption in Modbus mode <3,6 mA.
7.2.2. Shielding, equipotential bonding
A cable shield (green cable) is led out of the probe power supply and measurement cable.
Connect the shield on one side at the probe supply point.
10
Signal output
Type of connector
SHIELD
+
- (GND)
RS-485 A +
RS-485 B -
Output signal
MODBUS RTU
MODBUS RTU
4...20 mA
Wire colour
Green
Red
Black
Blue
Yellow
MIN. Power supply
voltage
4 V DC
4 V DC
5 V DC
MAX Power supply
voltage
28 V DC
10 V DC
28 V DC
Revision 01.A.001/2021.09