IO.PCE-28....PC-29.Exd
Electromagnetic fields (radiated interferences):
PN-EN 61000-4-3
80...2000MHz - 10V/m; ...2700MHz - 1V/m; Criterion A;
Fast electrical transient conditions (Burst):
PN-EN 61000-4-4
± 2kV supply lines; ± 1kV signal lines; Criterion B;
Surges:
PN-EN 61000-4-5
± 0,5kV (±1kV) signal lines - enclosure; ± 1kV (±2kV) supply lines - enclosure; Criterion B;
10.3.2.

Electromagnetic compatibility, emissions

Measurements acc. to CISPR 16-1, CISPR 16-2, class B;
Distance of antenna 3m, quasi-peak measurements:
Radiation:
0,15...30MHz; 80-52dBµV/m;
30...2000MHz; <54dBµV/m;
Inductions:
0,01...0,15MHz; 96-50dBµV/m;
0,15...0,35MHz; 60-50dBµV/m;
0,35...30MHz; <50dBµV/m;
10.3.3.

Mechanical immunity

Shocks:
PN-EN 60068-2-27, 31
50g/11ms
Sinusoidal vibrations:
PN-EN 60068-2-6, Fc test;
to 1,6mm; 2...25Hz;
to 4g for 25...100Hz;
10.3.4.

Electrical Isolation

>100MΩ @110V DC
10.3.5.

Insulation strength

75V AC (110V DC), 1 min
10.3.6.

IP protection ratings

Acc. PN-EN 60529:2003
- IP68 – for transmitters designed to measurement of underpressure or absolute pressure.
- IP66 – for transmitters designed to measurement of pressure.
16
04.A.004