A red alarm LED is provided on the call point. This
LED is controlled independently of the call point, by
the control panel.
Once activated, the XP95 Manual Call Point can be
reset by inserting the reset key into the front facing
LED, turning clockwise until a positive click and reset
occurs.
The isolated version of the XP95 Manual Call Point
incorporates a short circuit isolator which will ensure
its operation in the event of a short circuit fault on
the loop. Isolator operation is indicated by a yellow
LED. For further details of the isolator refer to data
sheet PP2090, available on request.
This Manual Call Point helps reduce installation
time as all the initial installation cabling is wired to
a removable terminal block which fits neatly in the
back of the Call Point.
DIMENSIONS AND WEIGHT
Indoor
88mm x 88mm x 59mm
DIMENSIONAL DRAWING
180g
88mm
TECHNICAL DATA
Supply voltage
Communications Protocol
Operating temperature
Humidity (no condensation)
IP rating
Current Consumption (max) at 24V DC
Power Up Surge (1s typical)
Quiescent
Alarm current (LED On)
Complies with EMC Directive 2004/108/EC
Red version complies with EN54–11:2001
EN54-17:2005 (Isolated version)
EMC DIRECTIVE 2004/108/EC
The Manual Call Point complies with the essential
requirements of the EMC Directive 2004/108/EC,
provided that it is used as described in this data
sheet.
A copy of the Declaration of Conformity is available
from Apollo on request.
Conformity of the Manual Call Point with the EMC
Directive does not confer compliance with the
directive on any apparatus or systems connected
to it.
CONSTRUCTION PRODUCTS DIRECTIVE 89/106/
EEC
The Manual Call Point complies with the essential
requirements of the Construction Products
Directive 89/106/EEC.
17-28V DC
5 - 9V Peak to Peak
-40°C to +70°C
0-95%RH
45
1mA
100µA
4mA