AddSecure Edge RT7020 Enterprise Manuel de l'utilisateur - Page 6

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} AddSecure Edge RT7020 Enterprise. AddSecure Edge RT7020 Enterprise 11 pages.

AddSecure Edge RT7020 Enterprise Manuel de l'utilisateur
Alarm transmission
Transmission started is indicated by LED2 (transmission via Ethernet) or
LED3 (transmission via radio) starts blinking with a frequency of 5 times per
second. Positive acknowledgment from the receiver is indicated by both
LED2 and LED3 blinks 3 times with a frequency of 1 time per second, while
negative acknowledgment is indicated by LED4 (red) blinks 3 times with a
frequency of 1 time per second.
Testing
The system should be tested at least once a year. For test of fire alarm
transmission, activate input 1 on the Edge RT7020.
For test of fault transmission, activate input 2 on the Edge RT7020.
To test internal fault states of the Edge RT7020 apply appropriate
conditions. For instance, to test the alarm for Ethernet error, remove the
Ethernet cable from its connector block.
6 Edge RT7020 Enterprise– programming and commissioning
All programming files for the Edge RT7020 are created in the web portal
Edge Manager. The Edge RT7020 is then programmed and commissioned
easily directly from the portal.
6.1

Checklist on premises

Alarm transmission via IP means that the Edge RT7020 must have access to
the Internet. Either via radio, via fixed Ethernet, or both. Please ensure the
following before going out to the site.
Positive acknowledgment from the receiver, meaning successful
transmission, is also indicated with REL5 being closed for 2 seconds.
Absent or negative acknowledgment by the receiver is indicated by the
normally opened REL4 being closed for 2 seconds.
System failure, either a total loss of communication (alarms cannot be
delivered via any of the communication paths) or tamper on one of the
inputs, is indicated by the normally closed REL1 being held open.
If the Edge RT7020 is to be connected to the customer's local network,
contact the IT department and inform them that an IP-terminal shall be
connected to the network. If the Edge RT7020 is to be programmed with
fixed IP parameters, ask for an IP-address, default gateway and net mask for
the network.
NOTE: Edge RT7020 also supports DHCP which means that the terminal can
automatically obtain the necessary information when connected to the LAN.
Make sure the correct ports have been opened, for outbound traffic, in the
customer's firewall.
- Receiving port number of the Connect platform (TCP)
- Port 1883 (TCP) for commands to the Edge Manager portal
- Port 4443 (HTTPS) for downloading and delivery of data to and from the
Edge Manager portal
6