Data Aire DAP III Manuel d'instructions - Page 13

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions pour {nom_de_la_catégorie} Data Aire DAP III. Data Aire DAP III 13 pages. Bacnet integration

Data Aire, Inc. DAP

4.4 Multi-State Value Objects

4.4.1 Readable fields

Object-identifier
Object-name
Object-type
Present-value

4.4.2 Object List

Object Name
Person To Contact
(Optional)
Reset Mode Warning
Water Under Floor Alarm Action
No Water Flow Alarm Action
(optional)
Energy saver Lockout Time
(optional)
Auto flush Timer
(Optional)
Unit on/off Control

4.5 References

ANSI/ASHRAE Standard 135-2001, BACnet - A Data Communication Protocol
for Building Automation and Control Networks
Engineering Document - 600-000-460
TM
III BACnet Integration Instructions
Status-flags
Event-state
Out-of-service
Number-of-states
Instance
Object Description
# MSV
13
Information of the person to contact
on the alarm event. This requires a
factory-preprogrammed message.
14
Loss of power or Unit restart warning
message
17
Water under floor alarm action
setting, menu 4-9 of the DAP III
panel. This can be set to unit
shutdown or compressor lock-out
18
No water flow alarm action setting,
menu 4-10 of the DAP III panel. This
can be set to compressor lock-out or
none. This requires an optional water
flow sensor.
19
Energy saver lockout time delay once
the DX cooling comes on. This is set
on menu 3-8 of the DAP III panel.
Energy saver option required
1001
Auto flush Timer setting. This setting
only applies when an optional
Infrared humidifier is used.
1002
This point controls the unit on/off.
The default setting value is 1; unit is
ON. Changing the setting value to 2
will turn the unit OFF. Default =1
(ON).
Page 13 of 13
Present-
value
Writeable
No
No
No
No
No
Yes-
Unsigned
value
Yes-
Unsigned
value