Elseta IOMOD 16DI Manuel de l'utilisateur - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} Elseta IOMOD 16DI. Elseta IOMOD 16DI 17 pages.

Elseta IOMOD 16DI Manuel de l'utilisateur

1. Introduction

IOMOD 16DI is small sized stand-alone Modbus (RTU) or
IOMOD is used for industrial applications, where digital signaling is used and robust communication
is needed. IOMOD is ideal solution for applications such as data acquisition, observation, process
monitoring, testing and measurement at remote places. It is controlled over Modbus or
5-103
protocol, and can be used with any SCADA system.

2. Features

16 digital inputs with configurable active signal polarity, or input inversion; Pulse count and ON
time count
Galvanically isolated inputs
Configurable over USB
Drag And Drop firmware upgrade over USB
RS485 communication
LED input indications, + Data transmission (Rx and Tx) indication.
Small sized case with removable front panel
DIN rail mount
Operating temperature: from -30 to +70°C
Power Requirements: 12-24 VDC

3. Device working information

IOMOD 16DI uses Modbus (RTU) or
device can be changed by uploading corresponding firmware. Default communication settings are: 9600
baudrate, 8N1, Slave address - 1.
a. MODBUS working information
To read all input status, send 02 Modbus command (Read Discrete Inputs) with resolution of first register
(0) and size of 16. Returned value will show 16 input states.
To read all input registers, send 04 Modbus command (Read input registers) with resolution of first
register (0) and size of 48. Returned data will show pulse count (first register) and ON time (2
registers) for each input – pulse count of input #2 will be at register 4
as seconds. ON time and pulse count will increase when input pulse is longer than Filter time, which is
configured by user in USB terminal menu. Shorter pulses will be ignored in both pulse and ON time
registers.
To invert input states by software, configure device over USB terminal. Useable Modbus commands
shown in table below.
IEC 60870-5-103
protocol over RS485 interface. Protocol used by
V1.1 | ELSETA | Introduction
IOMOD 16DI
IEC 60870-5-103
digital input controller.
th
, and so on. ON time will be shown
4/14/2017
IEC 60870-
nd
rd
and 3
5