Elsner Leak Spécifications techniques et instructions d'installation - Page 2
Parcourez en ligne ou téléchargez le pdf Spécifications techniques et instructions d'installation pour {nom_de_la_catégorie} Elsner Leak. Elsner Leak 7 pages. Leakage sensor for water and pipe breakage reporting
1.
Description
The Leakage sensor Leak includes an evaluation unit and a probe. If there is water
between the electrodes of the probe, the evaluation unit produces an acoustic alarm.
Additionally, the alarm output of the evaluation unit switches on. The output can be
used to transmit the alarm signal to other systems (e.g. klaxons, light indicators, stop
valves, building control system, alarm system). The changeover contact design of the
output makes it possible to detect wire breakage in the alarm line by suitable systems.
Functions:
•
Detection of water on the probe
•
Acoustic alarm signal by the evaluation unit during a water alarm (sustained
beeping tone). Short beeping during the follow-up time (1 minute after the end
of the alarm).
•
Output for alarm reporting (potential-free changeover contact)
1.1. Deliverables
•
Evaluation unit with mains power supply
•
Probe with BNC cable
•
Cable guide for alarm output
1.2. Technical specifications
1.2.1. Analysis unit
Casing
Colour
Installation
Protection category
Dimensions
Weight
Ambient temperature
Ambient humidity
Operating voltage
Power consumption
Probe input
Alarm output
The product is compliant with the provisions of EC guidelines.
Leakage sensor Leak • Version: 03.08.2017 • Errors and technical modifications subject to change without notice.
2
Plastic
Grey
Surface mounted
IP 20
approx. 118 × 86 × 65 (W × H × D, mm),
approx. 460 g
Operation -20...+70 °C, storage -55...+90°C.
max. 95 % RH, avoid condensation
230 V AC, 50 Hz
no alarm:
approx. 1 W
with alarm: approx. 4 W
1 x electrode probe,
plug-in BNC terminal
1 × potential-free changeover contact,
max. 230 V AC / 3 A,
max. 30 V DC / 3 A,
Connector NC/Com/NO
Description