Elsner KNX PS640-IP Installation et réglage - Page 9
Parcourez en ligne ou téléchargez le pdf Installation et réglage pour {nom_de_la_catégorie} Elsner KNX PS640-IP. Elsner KNX PS640-IP 20 pages. Power supply system with ethernet interface
Operation (Settings at the Device)
Starting position
elsner elektronik
KNX PS640-IP
Normal Operation
Diagnostics >
The following may be read off and set on the display of the Power Supply System KNX
PS640-IP:
·
Reset of a line
·
Recall of the data memory with operating hours, overcharge, external electrical
surge, internal electrical surge, short circuit and excess temperature
·
Recall of the operating data bus voltage, bus current and temperature
·
Language of display
The backlight of the display will be switched off automatically if the temperature inside
the housing exceeds 50°C. Thus a high thermal load is avoided.
Line reset
elsner elektronik
KNX PS640-IP
Normal Operation
Diagnostics >
Line Reset
Data Memory >
Operating Data
Language
Reset: Yes
No
30 seconds
Reset not active!
Yes:
No:
30 seconds:
With key
, you return to the previous menu level.
In starting position, press key
Press key
> ™
"Line reset".
>
Move the cursor (flashing rectangle at right edge) to
™
the desired setting with the keys
with key
Reset is activated. The line is switched to neutral and shorted. The
basic setting displays: "Reset is active!"
Reset not activated. The power supply system works in normal
operation.
A reset of 30 seconds is started. Afterwards, the line is supplied
with voltage as usual. During the reset state, which lasts 30
seconds, the basic setting displays: "Reset active: XX sec"
(countdown).
once more in order to get into the sector
.
once.
or
and confirm
9