elsner elektronik 70241 Spécifications techniques et instructions d'installation - Page 3

Parcourez en ligne ou téléchargez le pdf Spécifications techniques et instructions d'installation pour {nom_de_la_catégorie} elsner elektronik 70241. elsner elektronik 70241 9 pages. Combined indoor sensor

Configuration is made using the KNX software ETS. The product file, the data sheet
and the manual can be downloaded from the Elsner Elektronik homepage on
www.elsner-elektronik.de in the "Service" menu.

1.0.1. Scope of delivery

Housing with display, buttons and sensor board
CO
sensor unit
2
Base plate
You will need in addition (not supplied):
Socket Ø 60 mm, 42 mm deep
Frame (for element 55 x 55 mm), suitable for the switching programme used in
the building

1.1. Technical specifications

Housing
Colours
Mounting
Protection category
Dimensions
Total weight
Ambient temperature
Ambient air humidity
Operating voltage
Bus current
Data output
BCU type
PEI type
Group addresses
Allocations
Communication objects
CO
measurement range
2
CO
resolution
2
CO
accuracy*
2
Temperature measurement
range
Indoor Sensor KNX AQS/TH-B-UP • Status: 07.11.2013 • Technical changes reserved. Errors reserved.
3
Plastic material (partly lacquered)
• White glossy (similar to RAL 9016 Traffic White)
• Aluminium matt
• Anthracite matt
• Stainless steel
• Special colours on request
Ø
In-wall (in socket
IP 20
Housing approx. 55 x 55 (W x H, mm),
mounting depth approx. 15 mm,
base plate approx. 71 x 71 (W x H, mm)
approx. 72 g
Operation -10...+50°C, storage -20...+60°C
max. 95% R. H., avoid bedewing
KNX bus voltage
max. 10 mA
KNX +/- bus terminal plug
Own micro controller
0
max. 254
max. 254
253
0...2000 ppm
1 ppm
± 50 ppm ± 3% of the measuered value
-10...+50°C
60 mm, 42 mm deep)
Description