AC MGA0800/A1 Manuel de l'utilisateur - Page 12

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} AC MGA0800/A1. AC MGA0800/A1 16 pages.

Icon
Definition
T01
Cabinet internal temp-
erature
T02
Evaporator temperature
T03
Condenser temperature
T04
Cabinet internal humidity

5.3 Display

Under running, the main interface 8.8.8 displays real temperature value in cabinet
After boot, in any interface, if there has no keyboard operation in the continuous 60s,
automatically return to the main interface
self-test
5.4 Start
In the running states, the self-checking function can be activated by continuous pressing
seconds.
When Self-check, the screen will be full display for 1S, and then will normally display cabinet
temperature, while the boot icon will blink.
6

Running

6.1 Check before start running

There are not obvious blockages near the internal cycle air inlet and outlet of the
1)
air conditioner.
The input power cables and other signal cables have been connected reliably
2)
and correctly.
Main interface
Icon
Definition
E01
Cabinet internal high
temperature alarm
E02
Cabinet internal low
temperature alarm
E03
Cabinet internal tempErature
sensor alarm
E04
Evaporator tempErature
sensor alarm
E05
Condenser tempErature
sensor Alarm
E06
Evaporator- frozen alarm
E07
System high pressure alarm
11
Code input interface
(User:001)
Icon
Definition
P01
Refrigeration starting temperature setting
25~45
Size:
P02
Refrigeration return difference setting
3~10
Size:
P03
High temperature alarm setting
25~45
Size:
P04
Low temperature alarm setting
30~60
Size:
P05
Heating starting temperature setting
~15
Size:-30
P06
Heating return difference setting
~15
Size:5
P07
Communication address setting
0~255
Size:
for 3
SET