Measurement range temperature:
Measurement range wind:
Measurement range brightness:
The following standards were referenced with regard to evaluating electromagnetic
compatibility of the product:
EN 60730-1:2000-11 + A11:2002
The product has been tested by an accredited EMC laboratory according to the
abovementioned standards.
Weather Station P03/3-RS485 • Version: 11.10.2011 • Subject to technical alterations. Errors excepted.
-40...+80°C
Resolution: 0.1°C
Accuracy:
±1.5°C at -25...+80°C
0...70 m/s
Resolution: <10% of the measured value
Accuracy: ± 25% at 0...15 m/s,
at an angle of attack of 45°, pole mounting
0...99 000 lux
Resolution:
1 lux
at 0...120 lux
2 lux
at 121...1 046 lux
63 lux at 1 047...52 363 lux
423 lux at 52 364...99 000 lux
Accuracy: ± 35%