elsner elektronik 40111 Spécifications techniques et instructions d'installation - Page 3
Parcourez en ligne ou téléchargez le pdf Spécifications techniques et instructions d'installation pour {nom_de_la_catégorie} elsner elektronik 40111. elsner elektronik 40111 11 pages. Indoor sensor and ventilation control
1.1. Technical data
Housing
Colours
Mounting
Protection category
Dimensions
Total weight
Ambient temperature
Ambient humidity
Operating voltage
Power consumption
Temperature measuring
range
Temperature resolution
Temperature accuracy*
Humidity measuring range
Humidity resolution
Humidity accuracy
Ventilation outputs
Inputs
Measuring value outputs
(TH PF-U only)
* Please note the information on measuring accuracy below.
The product conforms with the provisions of EU directives.
1.1.1. Measuring accuracy
Follow the instructions in chapter Installation position to avoid sources of interference
and to ensure the specified accuracy of the sensor.
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated by reducing the measured temperture by the
self-heating of 0.7°C. The indicated indoor temperature measured value approches the
Plastic (partially painted)
• bright white (similar to RAL 9016 traffic white), no.
40100
• matt aluminium, no. 40101
• matt anthracite, no. 40102
• stainless steel, no. 40103
• special colours on request
Flush mounting
(wall mounting in junction box
IP 20
Housing approx. 55 x 55 (W x H, mm),
Mounting depth approx. 15 mm
Base plate approx. 71 x 71 (W x H, mm),
approx. 65 g
Operation -10...+50°C, storage -20...+60°C
max. 95% RH, avoid condensation
24 V DC ±20%
max. 16 mA
-10...+50°C
0.1°C .
± 0.4°C at 25°C
0...95%
0.1%
± 5% rF
2 semi-conductor outputs, open collector
max. 50 V AC/DC, 100 mA
2 button inputs (with +24 V supply)
Temperature 0...10 V (0 V = -10°C, 10 V = +50°C),
Humidity 0...10 V (0 V = 0%rF, 10 V = 100%rF).
100 Ω internal, max. load 5 kΩ
Ventilation Controls TH PF(-U)
Status: 19.04.2016 • Technical Changes and Errors excepted.
3
Description
R
60 mm, 42 mm depth)