Dataprobe iBoot-IO-OFF Manuel
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Dataprobe iBoot-IO-OFF. Dataprobe iBoot-IO-OFF 7 pages.
The iBoot-IO is a remote controlled power On / Off switch. One external control input is used to switch the
power ON and OFF. The iBoot-IO also provides a feedback circuit to verify the current power status. iBoot-IO
handles worldwide power from 105-240VAC. It is capable of switching up to 12 Amps at 120VAC and 10
Amps at 220 VAC. Screw terminals provide connection to the contact closure control and feedback circuit.
Power connections are made using supplied IEC-320 to NEMA 1-15 cables.
1.1.
Covered Models
Four models are covered in this document. They differ in the type of input circuit used to control the power and
the default status of the power outlet when no control is provided.
SKU
Model
1410037
iBoot-IO
1410039
iBoot-IO-OFF
1410044
iBoot-IO-LS
1410045
iBoot-IO-OFFLS
2.1.
Connect Powered Device
Connect the device to be powered ON and OFF to the IEC receptacle marked Switched Outlet. An IEC 320 to
North American (NEMA 5-15) power cord is included for connecting the iBoot-G2 outlet to the device to be
controlled.
Make sure that the combined load of all controlled devices does not exceed 12 Amps for 105-
125VAC or 10 Amps for 210-240VAC.
Connect Power Mains Connect the supplied power cord to the connector labeled AC Input, and the other end
to your AC source. If a power cord with a different terminating plug is required, be sure it is properly rated and
meets all the required local electrical standards.
Other Power Cords
Sourced Locally
1. General Description
Default Power
Control Input Type
ON
Dry Contact
OFF
Dry Contact
ON
+3 to +12 VDC
OFF
+3 to +12 VDC
2. Connections
Connect to Power Mains using
Supplied Cord
Power Switch
Contact Control
Connect Powered Device using
Supplied Cord