DV Power TRT30C Manuel - Page 12

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} DV Power TRT30C. DV Power TRT30C 19 pages. Three-phase transformer, turns-ratio test instrument

TRT30C
When generating a true three-phase test voltage, the TRT30C generates and provides a true three-phase
excitation test voltage to three transformer primary windings. The induced three-phase voltages across the
unloaded transformer windings are measured and the transformer turns ratio is calculated.
Test voltage of 8 V is recommended for current transformers (CT) testing. For testing distribution or power
transformers it is recommended to use the highest test voltage of 80 V. In addition, test voltage of 40 V can
also be used. Pressing
pressing
.
ENTER
The TRT30C automatically detects if it is connected to a DC power supply. It also automatically detects if
the power supply frequency is 50 Hz or 60 Hz. The frequency of the output voltage is the same as the
frequency of the power supply of the TRT30C. In case the TRT30C is connected to a DC power supply, the
user has to choose the frequency of the output voltage to be either 50 Hz or 60 Hz.
After the test voltage (and frequency) is selected, the user can select a memory location manually (Test
Reading and Test Record).
Test Reading or Test Record is performed by using
Test Reading can contain, for example, all the test results obtained in one tap changer position of the
transformer. Test Record can contain the results of all tap changer positions, or the complete results
obtained from one transformer.
Note: Manual selection of record/reading will delete results from the existing memory locations.
Once these parameters are defined, pressing
Figure 3-3:
The READY state
before the test
If one of the values has to be changed, press
The flashing green LED indicates that the TRT30C is now ready to start the test. Press
During the test, the red LED glows continuously signaling that the test voltage is applied. Pressing
(the CONFIGURATION menu is displayed) will interrupt (abort) the test. When the test is completed, the
TRT30C displays the test results. To scroll between all the results press
viewed, press
to test the next tap or to finish the test.
ENTER
If the AVGD option in the CONFIGURATION menu is selected, the TRT30C will try to automatically detect a
vector group of the transformer being tested. The user will be asked whether to continue the test with a
detected vector group or to select one of the available vector groups. If for some reason the vector group
cannot be detected, the device will display the message "Unable to detect vector group" and the test will be
aborted. Once the vector group is detected and confirmed, the TRT30C continues with the test. After the
test is finished, the TRT30C displays the test results. To scroll between all the results, the user will press
. Once all the results are viewed, the user can choose whether to test the next tap or to finish the
ENTER
test.
M-T030CN-203-EN
the user selects the value of his/her choice and then confirms it by
UP/DOWN
is used to scroll between Test Reading and Test Record use. Selection of
SET
ENTER
STOP
. Pressing
UP/DOWN
ENTER
changes the status to the READY state.
to return to the previous menu.
12
Getting Started
confirms a selection.
to run a test.
START
. Once all the results are
ENTER
STOP