1. INTRODUCTION
1.1 Prefix
Dear customer, thank you for choosing the AUM-2000 micro inverter from
Austa. We hope you will find our products meet your need for renewable
energy. Meantime, we appreciate your feedback regarding our products.
1.2 Grid-tied PV System
Grid-tied PV system consists of PV panels, grid-tied inverter and junction boxes.
The DC output from the PV panels is converted into AC energy and feedback to
the grid through the AUM-2000. AUM-2000 PV micro inverter contains isolation
transformer with basic insulation between PV input and AC grid output.
1.3 How to Use This Manual
This manual provides detailed product information and installation instructions
for the AUM-2000 micro solar inverter. Please read through this manual before
installation and operation.
WARNING: This indicates a situation where failure to follow instructions may be
a safety hazard or cause equipment malfunction. Use extreme caution and
follow instructions carefully.
1.4 Label
Label is located on the side of the inverter. The information on the label includes
technical data as well as type and serial number of the device. Safety instructions
are listed and explained below:
Danger!
The term "danger" describes an issue which, if ignored can cause
personal injury.
Attention!
With the term "attention" a circumstance is listed which may
cause property damage if disregarded.
Instructions for use!
Under "Instructions for Use", it is pointed out that installation and
operating instructions are to be read and understood before
installation or repair.
Caution, hot surface!
Under "Caution, hot surface", it should be noted that surfaces of
equipment may be hot and create a burn hazard.
Special disposal instructions!
With "Note Separate Disposal", it is pointed out that this product
may not be disposed of with normal garbage. An improperly
conducted disposal can lead to damage to the environment.
CE mark
The product complies with essential requirements of relevant
directives of EU
02
2. SAFETY INSTRUCTION
WARNING:
PLEASE READ THIS MANUAL BEFORE INSTALLATION. ANY DAMAGE TO THE PRODUCT DUE TO NOT
FOLLOWING THIS MANUAL IS NOT COVERED BY THE WARRANTEE.
ALL THE INSTALLATION SHOULD BE DONE BY CERTIFIED ELECTRICIAN.
BESIDES THE CABLE CONNECTORS, NOTHING INSIDE THE INVERTER SHOULD BE MODIFIED.
ALL INSTALLATION SHOULD FOLLOW THE LOCAL ELECTRIC CODES. FURTHER PROTECTION ON THE
AC WIRING FROM THE INVERTERS SHOULD BE PROVIDED AND MAY BE REQUIRED BY LOCAL AND
NATIONAL WIRING REGULATIONS. THIS PROTECTION IS LIKELY TO INCLUDE RESIDUAL CURRENT
DEVICES, EARTH FAULT MONITORS AND CIRCUIT BREAKERS. THIS PRODUCT MAY CAUSE AC
CURRENT WITH A DC COMPONENT.
IF A RESIDUAL CURRENT-OPERATED PROTECTIVE DEVICE
(RCD) OR A MONITORING DEVICE (RCM) IS USED FOR PROTECTION IN CASE OF DIRECT OR
INDIRECT CONTACT, ONLY AN RCD OR RCM OF TYPE B IS ALLOWED ON THE AC SIDE OF THIS
PRODUCT.
NEVER DISCONNECT PV MODULE FROM THE MICRO-INVERTER WITHOUT FIRST ISOLATING THE AC
MAINS.
ALL PV CONNECTORS AND AC CONNECTORS ARE FORBIDDEN TO BE DISCONNECTED
UNDER LOAD BEFORE SWITCHING OFF THE CIRCUIT BREAKER ON THE AC BRANCH.
PLEASE CONTACT AUTHORIZED SERVICE AGENTS FOR ANY SERVICE WORK.
AU-1P20002G
IS A GRID-TIED SOLAR INVERTER.
UTILITY COMPANY TO CONNECT IT TO THE POWER GRID.
AU-1P20002G
DOES NOT INCLUDE COMPONENTS THAT CAN BE SERVED BY CUSTOMERS.
WARNING:
WHEN THE PHOTOVOLTAIC ARRAY IS EXPOSED TO LIGHT, IT SUPPLIES A DC VOLTAGE TO THE
MICRO-INVERTER.
3. FCC COMPLIANCE
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following
measures:
● Reorient or relocate the receiving antenna.
● Increase the separation between the equipment and the receiver.
● Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
● Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for
compliance may void the user's authority to operate the equipment.
IT MAY REQUIRE APPROVAL FROM LOCAL