Bender ATICS DIO Series Manuel de démarrage rapide - Page 9

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Bender ATICS DIO Series. Bender ATICS DIO Series 13 pages. Automatic transfer switching devices for safety power supplies

9. Menu mode: Operation and setting

Press the "MENU" button to open the main menu.
– Use the arrow buttons to go up resp. down one menu level.
– Press the "↵ " button to confirm the selected menu item.
– Press the "ESC" button to leave the menu.

10. Menu overview

Main menu
Meaning
Exit
Exit menu mode
1. Alarm/meas.
Displays current status messages, alarm
values
messages and measured values
2. Changeover
Displays information on the changeover
function (number, test)
3. History/Logger Displays logger information
4. Settings
Various settings for this device
5. Control
Run TEST and RESET for this device
6. Digital input
Display voltage level of the digital inputs
7. Info
Display information on device type and
firmware versions
ATICS-DIO_D00080_02_Q_XXEN/04.2017
Submenu:
Meaning/Setting
1. History
Alarm messages of this device and tests which have been
performed: value and time
2. Data logger
Displays the history of measured values: Line 1, Line 2, posi-
tion, load current in the TN system I(3)
3. Config.logger
Shows the history of the "Settings" menu: value and time
4. Test data logger
Displays the history of the tests of the changeover switch
carried out
5. Service logger
Displays the history of the service activities carried out
1. Changeover
Setting the date and time, system, switching back interlock-
ing function, preferred supply, generator, test and service
interval
2. Voltage
Delay times, voltage ranges, hysteresis
3. Current
Short-circuit detection
4. Relay
Mode of operation and relay mode
5. Digital Input
Mode of operation, function, delay
6. Data logger
Modify, overwrite, delete
7. Language
Deutsch, English, Francais
8. Interface
Setting the BMS bus address for this device, allow to change
settings via BMS bus, allow to run a test via BMS bus.
9. Clock
Format, date and time setting
10. Password
Enable resp. set password for settings and test
11. Service
Reserved for settings to be made by authorised Bender Serv-
ice personnel.
1. TEST
Changeover, last changeover saved as a test, generator
2. RESET
Reset alarm messages, cancel the switching back interlock-
ing function, change the alarm value for the max. permissi-
ble number of changeover operations performed and the
max. permissible number of operating hours
ATICS-...-DIO Quick start
3