Bender ATICS-2-ISO Series Manuel de démarrage rapide - Page 7
Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Bender ATICS-2-ISO Series. Bender ATICS-2-ISO Series 8 pages. Automatic transfer switching devices with monitoring functions for unearthed safety power supplies - software version: d333 v1.3x, d334, v1.3x, d335 v1.0x, d308 v1.2x
Également pour Bender ATICS-2-ISO Series : Manuel de démarrage rapide (16 pages)
Main menu
Meaning
1. Alarm/meas. values Displays current status messages, alarm messages and measured values
2. Changeover
Displays information on the changeover function (number, test)
3. History/Logger Displays logger information
4. Settings
Various settings for this device
5. Control
Run TEST and RESET for this device
6. Digital input
Display voltage level of the digital input
7. Info
Display information on device type and firmware versions
11. Troubleshooting
If a fault occurs,
proceed as follows:
Fault/message
Failure Line xx
(xx stands for: 1, 2, AV, SV, UPS,
BSV), undervoltage or overvoltage
Failure line 2
Insulation fault
Overload
Overtemperature
CT connection
CT short-circuit
ATICS-2-ISO_D00046_02_Q_XXEN/09.2016
1.
Activate manual mode, if necessary.
2.
Make a note of what happened prior to the fault: operator
inputs, device error messages, ambient conditions, etc.
Description
Voltage is no longer available on Line 1 or Line 2
(Channel 1 = Line 1,
Channel 2 = Line 2)
Generator deliveres no voltage within the set time t(GenMax)
IT system has insulation fault
Current consumption too high
Temperature on the IT system transformer is too high
Generator delivers no voltage within the set time. Short circuit or
interruption of the connection cable was detected: Measuring
current transformer STW2 (T4), isolating transformer load, channel 10.
Submenu:
Meaning/Setting
Alarm messages of this device and tests which have been
1. History
performed: value and time
Displays the history of measured values: Line 1, Line 2, posi-
2. Data logger
tion, load current in the TN system I(3), insulation, trans-
former load
Shows the history of the "Settings" menu: value and time
3. Config. Logger
Displays the history of the tests of the changeover switch
4. Test logger
carried out
Displays the history of the service activities carried out
5. Service logger
Setting the date and time, system, switching back interlock-
1. Changeover
ing function, preferred supply, generator, test and service
interval
2. Voltage
Delay times, voltage ranges, hysteresis
3. Current
Short-circuit detection
4. IT system
Response values insulation, transformer load, temperature,
fault location
5. Relay
Mode of operation and relay mode
6. Digital input
Mode of operation, function, delay
7. Data logger
Modify, overwrite, delete
8. Language
Deutsch, English, Francais
9. Interface
Setting the BMS bus address of this device.
Allow the settings to be changed via the interface.
Allow a test to be run via interface.
10. Clock
Set date format and date and time
11. Password
Enable resp. set password for settings and test
12. Service
Reserved for settings to be made by authorised Bender
Service personnel.
1. TEST
Isometer, changeover, last changeover saved as a test, generator
2. RESET
Reset alarm messages, cancel the switching back
interlocking function, change the alarm value for the max.
permissible number of changeover operations performed
and the max. permissible number of operating hours
ATICS-2...-ISO Quick start
3.
Keep the device type and device serial number to hand.
4.
Speak to Bender Service, describe the type of fault
and quote the three-digit error code.
Remedy
→
Measure voltage on Line xx.
→
Check cause.
→
Eliminate fault on the system.
→
Check the setting for voltage and hysteresis.
→
Look for insulation fault.
→
Eliminate fault on the system.
→
Check setting for transformer load current.
→
Switch off any loads which are not urgently needed.
→
Switch off any loads which are not urgently needed.
→
Check connecting wire of measuring current trans-
former
3