GAC LSM201 Manuel - Page 2
Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} GAC LSM201. GAC LSM201 11 pages. Load sharing modules
3
INSTALLATION
•
An overspeed shutdown device, independent of the governor system, should be used to prevent loss of engine control
which may cause personal injury or equipment damage.
•
Do not rely exclusively on the governor system electric actuator to prevent overspeed. A secondary shutoff device, such
as a fuel solenoid must be used.
Mount the LSM200 Series Module in the generator set control cabinet with the other dedicated control equipment. Locate the load shar-
ing, synchronizer, and speed control devices as close together as possible to minimize inter-connection cable lengths.
All generator sets that are to be synchronized must be tested independently for their maximum capabilities. Information should be gath-
ered for reference if operational issues arise after installation of this product.
Read this entire installation manual before starting installation of this product.
LSM200 Series Load Sharing Modules 6-2021-B1 PIB4100
2
Governors America Corp. © 2021 Copyright All Rights Reserved
Dimension Units
in
[mm]