time by continuously testing the internal impedance status, avoids any possible risk of damages and grants also a
permanent, reliable and safe connection of the battery to the power supply. The system, through a battery
stimulation circuit with algorithms of evaluation of the detected parameter, is able to recognize sulphated batteries or
batteries with a short-circuited element.
Battery Test: Automatic. Every 60 sec. check battery connection. Every 220 minute in trickle charge, make the test of
the battery efficiency. The fault is signaled with relay BATTERY FAULT commutation and DIAGNOSIS led blinking.
Diagnostic Type Checks
Check for accidental disconnection of the battery cables:
All In One detects accidental disconnection and immediately switched off the output BATTERY.
Battery not connected:
If the battery is not connected no output BATTERY.
Test of quality wire connections:
During trickle charge the quality (resistance) on the battery connection is checked every 20 sec. This to detect if the
cable connection has been properly made.
Battery in Open Circuit or Sulphated:
Every 220 minute. All In One tests of internal impedance, in trickle charging mode.
Reverse Polarity check:
If the battery it is connected with inverted polarity, All In One is automatically protected.
Test of battery voltage:
Appropriate voltage check, to prevent connection of wrong battery types, more or less than the nominal voltage.
End of Charge check:
When the battery it is completely full, the device automatically switch in trickle charging mode.
Check for Battery Cells in short circuit :
Thanks to specific algorithms of evaluation, the CBI recognize batteries with cells in internal short circuit.
In trickle charge every 2 hours test of element in short circuit.
Diagnosis of battery and device:
All CBI devices support the user during installation and operation. A Blink code of Led DIAGNOSIS allows to
discriminate among various possible faults.
Error conditions, "Led BATTERY FAULT" ON and "Led DIAGNOSIS" blinking with sequence; see Display Signal
section.

Charging Curve:

Automatic multi-stage operation and real time diagnostic allows fast recharge and recovery of deep discharged
batteries, adding value and reliability to the system hosting the CBI device. The type of charging is Voltages stabilized
and Current stabilized IUoUo.
Four charging modes are identified by a flashing code on a Diagnosis LED.
To maintain the Output Load in lower Voltage state, don't put jumper FAST CHARGE, in this case no boost charge but
only Float charge.
Charging Type
State
Diagnosis LED
Trickle-Float
1 Blink/2sec
Absorption
1 Blink/sec
Boost-Bulk
2 Blink/sec
Recovery
5 Blink/sec
Battery Fault LED
OFF
OFF
OFF
OFF