GREAT PLAINS QM Series Manuel du propriétaire - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel du propriétaire pour {nom_de_la_catégorie} GREAT PLAINS QM Series. GREAT PLAINS QM Series 16 pages. Positive displacement fuel meter

CALIBRATION

The meter is accurately calibrated at the
factory for use with diesel fuel� Due to
differences in viscosity and flow rates,
the meter may require recalibration
to measure other fuels or to adjust
for inaccuracies� A gear replacement
kit is available (PN 139500-15, see
Illustrated Parts List section) to
convert the meter to unleaded fuels�
1� To adjust the calibration of the me-
ter, gain access to the calibration
screw by performing the following:
(see Figure 4)
2� Remove the back plate and the
(4) screws retaining it� The O-ring
seal under the plate must not be
damaged�
3� Using the 5MM hex L-wrench
provided with the meter, adjust the
calibration screw as required�
4� Note: The calibration screw set-
ting may have been adjusted at
the factory� The gasoline setting
is approximately fully closed (turn
clockwise)� Do not overtighten the
screw against the seat�
figure 4
5� Reinstall the plate, (4) screws
and the O-ring seal if removed�
Tighten (4) screws to 42-46 lb-in
[4�7-5�2 N
m] torque�

MAINTENANCE

The meter's strainer should be cleaned
at regular intervals, especially if reduced
flow is encountered�
Clean or Replace Strainer
1� Remove the socket screws at the
inlet fitting� Remove the fitting, O-
ring and strainer� (see Figure 5)
figure 5
2� The strainer rim is pressed into the
housing inlet but can be removed
by carefully grasping the end with
pliers and pulling with a wiggling
motion until free�
3� Using a fine brush, clean the strainer�
Replace the strainer as necessary�
4� Wipe the housing inlet clean and
reinstall strainer, pressing it into
the strainer bore� It is designed to
be field pressed back into place
using the end of a clean 1" pipe
nipple or similar tube tool using light
hammer taps�
CAUTION
The mesh strainer must always be
installed when operating the meter;
otherwise, particles may enter the
meter chamber and disrupt the
smooth operation of the oval gears�
5� Wipe clean the fitting and O-ring
groove� Coat the O-ring with oil or
light grease and seat into the fitting
groove�
6� Reinstall the inlet fitting and screws�
Tighten screws to 42-46 lb-in
[4�7-5�2 N
m] torque�
5