SECTION III

3.1 System Shut Off Procedure

If your system is not equipped with a bypass valve or any similar other
mechanism the entire system must be shut off. Precede the steps below with
shutting off your pump and draining the system.
1. Open the bypass valve.
2. Close the outlet valve completely.
3. Close the inlet valve completely. The filter is now isolated and the system flow
is bypassed.
4. Relieve any residual pressure in the filter housing by opening the flush valve.
5. Drain the remaining water from the filter body by loosening the cover nuts and
slightly opening the cover.

3.2 Periodic Checks

It is strongly recommended that annual checks be performed at the same time
every year.
1. Check filter and all connections for leaks.
2. Check the filter housing for paint damage
and corrosion. If required, clean the area
by sanding and reapply a thin layer of
paint and epoxy.
3. The system must be properly shut off as
described in "Section 3.1" before
performing the following checks. Do not
proceed until this has been complete.
4. Check the condition of all seals. Replace
any damaged or deteriorating seals.
5. Check the condition of the fine screen
assembly. If necessary, replace
according to "Fine Screen Assembly
Removal & Installation".
6. Check the dirt collector suction nozzles
height (See Figure 3). If necessary,
replace according to "Dirt Collector
Removal & Installation"

MAINTENANCE

Figure 3: Nozzle Height (44mm)