Automatic Heating Firex 55 Manuel d'utilisation - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Automatic Heating Firex 55. Automatic Heating Firex 55 12 pages. Biomass wood fired water heaters

Automatic Heating Firex 55 Manuel d'utilisation
User operating instructions
Using switch 12 it is not possible to turn the fan power
on and off.
- When the switch is on 0, the fan is not electrically
powered.
- When the switch is on
powered.
The top door is open to load wood and the
fan runs at full speed.
Light the wood as described in Chap. 6.6.
Opening the wood loading door activates a control
timer by means of an end-of-travel micro-switch. It has
a default value of 30 minutes which can be increased or
decreased by 30 minute increments (only by authorised
personnel).
If the boiler does not reach the minimum temperature
(approx. 65°C) within the required amount of time, the
fan and recirculation pump will switch off.
The panel is powered, but ... the boiler is not running.
Light the wood once again.
Heating temperature control
It is possible to control the temperature of the FIREX
boiler system water by turning the knob pos. 32
clockwise to raise it, and counter-clockwise to lower it.
Temperature is adjusted between a minimum of 75°C
and a maximum of 85°C.
Resetting the safety thermostat
IMPORTANT: The reset control of the FIREX boiler
safety thermostat is located on the front of the panel
board.
Thermostat pos. 31 resets operation of the wood-
fi red boiler.
To access it when the boiler blocks, unscrew the
plastic cap with a screwdriver; after having reset the
boiler, put the plastic cap back on.
, the fan is not electrically
5