Automatic Heating BCM Manuel d'utilisation - Page 4
Parcourez en ligne ou téléchargez le pdf Manuel d'utilisation pour {nom_de_la_catégorie} Automatic Heating BCM. Automatic Heating BCM 15 pages. Modulex boiler communications module
Modulex Controller Operation
Figure 1-5. Installing Resistor to Change Default Setpoint
1.4 BCM CONFIGURED AS PRIMARY
CONTROLLER UTILIZING MODBUS
The BCM can be configured as the Primary Controller, instead
of the E8, when it is connected to a Modbus Network. However,
the E8 must be disconnected from the e-Bus connection on
the BCM Board (see para. 1.4.3). All Modbus Networks are
implemented utilizing a "Master – Slave" scenario where only
one device, the "Master", can initiate a communication
sequence. However, BCMs can only function as "Slave"
devices on a Modbus Network. Therefore, the BCM must be
interfaced to an external controlling "Master". The "Master"
can be an Energy Management System (EMS)/Building
Automation System (BAS) developed by other manufacturers.
The following subordinate paragraphs provide descriptions
of Modbus Network operation and required wiring connections
between the BCM "Slaves and the controlling "Master" (EMS,
BAS).
Detailed information on the Modbus Function Codes, Input/
Holding Register Assignments and other Modbus
requirements supported by the BCM are provided in Appendix
B of this document.
1.4.1 OPERATING SCENARIO
Each Modulex Boiler is equipped with its own BCM to
allow Modbus Network monitoring and control. The Master
can control the Networked Modulex Boilers utilizing either
4
Set point
Ext sens
Open
82°C
71
°C
60
°C
47
49
°C
22
38
°C
27°C
Remote Setpoint or Modulation Level signaling.
In the event that the external control signal from the EMS
or BAS is lost, the BCM will assume control of the Modulex
Boilers if enabled by switch. When this occurs, the BCM
will maintain the boiler at a constant setpoint based on
the resistor installed between terminals 6 and 7 of
connector Y2 (see Figure 7-5). If the event occurs and the
2 positions switch is on 0 (disabled), the BCM Fault Relay
will be activated and the red Fault LED (DL2) will light.
1.4.2 PHYSICAL MODBUS RS485 WIRING
Modbus RS485 devices should be wired in a "Daisy-Chain"
configuration similar to the example shown Figure 7-6. DO
NOT wire the units in a "Star" configuration where all devices
are connected to a central point (node).
MASTER
SLAVE
SLAVE
#1
#2
Figure 1-6. Typical Daisy-Chain Modbus/RS485 Network
The physical wiring connections for a Modbus Network should
be made using shielded twisted-pair wire.
Modbus wiring connections are made at terminals 1 and 2 of
BCM connector Y2 as shown in Figure 7-7.
BCM FRONT VIEW
1-7. BCM Modbus (RS485) Connections
SLAVE
SLAVE
SLAVE
#3
#4
#5