3. GSC400 AC Calibration Utility

3.1 Main Screen

When you open the GSC400 AC Calibration Utility the window in Figure 4 will
appear. This window allows you to read or modify the 12 AC Sensing calibration
constants on the GSC400. Each value can range from -126 to 126.
It is highly recommended that you read and record the calibration
constants (click the Read Calibration button shown in the figure below)
before making any changes. Once you make a change it is non reversible.
Figure 4 – Calibration Utility Main Window
To read the calibrations click the large "Read Calibration" button. To change a
calibration constant enter the desired values in the boxes and click the "Set"
buttons beside each phase. Make sure that you have the correct COM port
selected under "Communication" menu at the top.