DynaGen ES53 Manuel d'installation et d'utilisation - Page 9
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} DynaGen ES53. DynaGen ES53 18 pages. Control module
17
Engine running output provides 300mA maximum. Engine Running output closes
to+12/24 VDC when the engine starts (speed > crank disconnect setting), and
opens when the engine stops. Flashing output indicates Crank Rest period.
18
Normal Disable to Transfer Switch (WHITE connection of 5-wire interconnect
harness)
19
Emergency Disable to Transfer Switch (RED connection of 5-wire interconnect
harness)
20
Ground connection to Transfer Switch (BLACK connection of 5-wire
interconnect harness)
Installation and User Manual for the ES53 Control Module
9