There are 3 main operating states for the Battery Charge Monitor, they are as follows:
IDLE:
Idle state is assumed when the unit is powered-up (power applied to +Battery terminal),
but not told to run (sense input has not gone below low voltage set point).
In Idle state, when sense input voltage drops below the LOW voltage set point, we
proceed to the Delay ON timing state.
DELAY ON TIMING:
The Delay ON timing state ensures that the Sensing input voltage is below the low set
point for a period of time. This delay prevents unnecessary starts of operating equipment.
The Delay on time is adjustable via an onboard DIP SWITCH. When the delay ON time
has elapsed, the BCM unit proceeds to Charging.
CHARGING:
In the charging state the BCM unit continually monitors for a high battery condition.
When the sensing input voltage goes above the HIGH voltage set point, the BCM unit de-
energizes the RUN relay and proceeds to the IDLE state of operation.
Operating & Installation Manual for Battery Charge Monitor (BCM)
SYSTEM OPERATING STATES
A. IDLE
B. DELAY ON
C. CHARGING