AirCycler g1 Manuel d'installation et d'utilisation - Page 4
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} AirCycler g1. AirCycler g1 11 pages. Ventilation controller
Également pour AirCycler g1 : Manuel de test d'installation (2 pages)
DAMPER LOCATION
The fresh air damper can be located anywhere in the inlet duct. Minimize the length of the inlet duct to improve air
flow and improve system efficiency. It is recommended that the damper be as close to the return air plenum and the
AirCycler® g1 controller as possible, and the inlet duct connect to the return plenum upstream of the system filter, and
down- stream of any duct mounted sensors.
DAMPER INSTALLATION
The damper may be installed in any position. It is recommended to install it with the motor at the 12 o'clock position if
mounted horizontally. Air may flow through in either direction, although it is recommended to install with the crimped
end as the outlet. Use care to avoid distorting the damper housing and provide adequate support. Upon system start
up be sure to set damper power switch to UP or AUTOMATIC position.
CHOOSE A FRESH AIR LOCATION
ASHRAE recommends that the fresh air intake be located at least 10 ft. from any source of pollutants, such as auto
exhaust, dryer exhaust, exhaust from any fuel-burning appliances, etc. Avoid installation near odor sources such as
garbage bins or barbecue grills. A minimum of 3 ft. above ground is recommended to avoiding ingress of leaf litter,
grass clippings, etc. Do not use a crawl space, basement, or attic as a source of intake air. Always be sure to comply with
local building codes and requirements regarding fresh air inlets.
Thermostat
AirCycler®
g1
4
Main Return
Duct
Motorized
Damper
Outside
Air Duct
Filter
REV 9/14/2016
AC DOC