Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Automation Direct PRODUCTIVITY 2000. Automation Direct PRODUCTIVITY 2000 8 pages. Analog input

Wiring Diagram
Thermocouple Input Circuits
Ungrounded/Shielded
Thermocouple
TC+
TC-
Grounded/Shielded
Thermocouple
TC+
TC-
Infrared
Thermocouple
TC+
TC-
NOTES:
1. Connect shield to thermocouple signal/ground only. Do not connect to
both ends.
2. Install jumper wire on each unused input,
TC+ to TC-.
3. With grounded thermocouples, take precautions to prevent having a
voltage potential between thermocouple tips. A voltage of 1.25V or
greater between tips will skew measurements.
4. Use shielded, twisted thermocouple extension wire that matches the
thermocouple type. Use thermocouple-compatible junction blocks.
Sales 800-633-0405
Voltage Input Circuits
TC+
4-wire
Voltage
TC-
Transmitter
Transmitter
AC or DC
Power Supply
TC+
Load Cell
or
TC-
Strain Gauge
Excitation
AC or DC
Power Supply
Voltage Divider
TC+
TC-
TC+
TC-
Schematic
www.productivity2000.com
INTERNAL
MODULE CIRCUITRY
TC1+
CH1 T/C
TC1-
INPUT
TC2+
CH2 T/C
TC2-
INPUT
TC3+
CH3 T/C
TC3-
INPUT
TC4+
CH4 T/C
TC4-
INPUT
TC5+
CH5 T/C
TC5-
INPUT
TC6+
CH6 T/C
TC6-
INPUT
TC7+
CH7 T/C
TC7-
INPUT
TC8+
CH8 T/C
TC8-
INPUT
3