Dynalite DBC410 Manuel d'installation - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} Dynalite DBC410. Dynalite DBC410 8 pages. 4 x 10a hf ballast controller

troubleshooting

Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite office. A
complete list of distributors worldwide can be found on the Internet at:
Please ensure that you have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
SYMPTOM
Dimmer does not operate at all. No Service LED
activity. Power supply indicator LED on PCB not lit.
Power supply indicator LED lit, but no Service LED
activity.
Dimmer will not respond to control panel push
buttons.
Dimmer operates properly but circuit breakers keep
tripping.
Fluorescent lights won't dim.
specification
Outputs:
Optional Maintained Output:
Protection:
Switching Device:
Control Inputs:
User Controls:
Internal Controls:
DyNet DC Supply +VE:
Preset Scenes:
Supply Terminals:
Output Terminals:
Cable Entries:
Diagnostic Functions:
Compliance:
Construction:
Dimensions:
DBC410 Installation Manual Rev K.doc Specifications and design subject to change without notice.
Dynalite Manufactured by WMGD Pty Ltd (ABN 33 097 246 921). All rights reserved. Dynalite, Dimtek, DyNet and DLight and associated logos are the registered
8
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
DBC410 Installation Manual Rev K.docx
PROBABLE CAUSE
Incorrect connection of Mains supply, or no
power available.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Control panel incorrectly wired or incorrect
configuration.
Instant tripping: - short circuit on load.
Delayed tripping: - Dimmer overloaded.
Wrong type of ballast or ballast incorrectly
wired. Control cable from DBC410 to ballasts
not installed.
Supply:
230V
50/60Hz Single Phase at 40A
±14%
4 x switched outputs at 10A
4 x signal control outputs, selectable to 1-10VDC and DSI
1 x Maintained NC output for testing battery packs in fixtures (fed from MCB A, total load
maintained output & Ch 1 is 10A)
4 x 10A single pole thermal magnetic circuit breakers
Relay 12A nom. (resistive) 120A surge
1 x RS485 DyNet serial port
1 x programmable dry contact AUX input
Service Switch
Diagnostic LED
Programmable Logic Controller
Dynalite Accessory Module enabled
90mA (supply for approx. 4 Smart Panels)
170
Line, Neutral – 2 x 4mm
Line, Neutral for each channels 1-8
2
2 x 4mm
max conductor size
Earth link bar provided
0V/DSI , +V/DSI for each channel
2
1 x 2.5mm
max conductor size
Mains – 1 x 75mm x 53mm removable gland plate
Data – 1 x 25mm dia. knockout
Device Online/Offline status
Circuit breaker trip reporting (optional)
Circuit run time tracking (optional)
CE, C-Tick
Alloy/Steel wall mount case with epoxy finish
Height 320mm x Width 225mm x Depth 75mm (excludes wall brackets)
Weight:
4.0 Kilograms
trademarks of Dynalite Intelligent Light Pty Ltd. Not to be reproduced without permission.
E-mail:
www.philips.com/dynalite
ACTION
Check power supply to dimmer. Check Line and
Neutral input connections.
Check supply voltage is at least 75% of rated
voltage. Check 5V & 12V terminal voltages, 5V
supply must be present. Disconnect network bus
and restore power. Replace control PCB.
Check operation of LEDs on control panel. Push
button on panel and study response of service
LED.
Check load wiring for short circuits.
Verify dimmer loading with current tester (don't
forget to de-rate for low power-factor loads and
transformer losses). Check that the breaker
terminals are tight.
Check ballast type. Check actual wiring against
ballast manufacturer's diagram. Check 1-10V/DSI
cable and settings.
2
max conductor size
Web: Philips.com/dynalite