AutomationDirect Stride SIO-MB04RTDS Manuel de l'utilisateur - Page 11

Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} AutomationDirect Stride SIO-MB04RTDS. AutomationDirect Stride SIO-MB04RTDS 12 pages. Temperature input module: rtd, 4-channel
Également pour AutomationDirect Stride SIO-MB04RTDS : Manuel de démarrage rapide (2 pages)

Analog Input

This page displays the values of the analog inputs in the unit of measurement defined by the "Input Type". Each input is electrically
isolated from all others and can be configured independently.
• Read: retrieves current value and break status from the device for all channels.
• Input Type (ref. "Input Type" registers): sets the desired type of sensor connected to the input. A channel can be disabled by
selecting "Disabled" as its input type.
• Value (ref. "Analog Input" registers): shows the current value of each analog input.
• Break (ref. "Break" register): indicates the connectivity status of the sensor. If a sensor is disconnected, a wire is broken or the
sensor is over temperature, a red indicator is shown under the break column at that channel.
• Offset: sets an offset value to be added to the raw sensor reading to calibrate the sensor.
• Set Same Input: sets all channels to the input type selected for the first channel (Analog In 0).
Click Save to apply and save all changes on the page.
SIO-MB04RTDS User Guide, 1st Edition
Stride Field I/O
10