AutomationDirect T1K-16ND3 Manuel de démarrage rapide - Page 4

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} AutomationDirect T1K-16ND3. AutomationDirect T1K-16ND3 8 pages. Dc input modules

1 - 8 0 0 - 6 3 3 - 0 4 0 5

Dimensions and Installation

It is important to understand the installa-
tion requirements for your Terminator I/O
system. This will ensure that the Terminator
I/O products work within their environmental
and electrical limits.
Plan for safety
This catalog should never be used as
a replacement for the technical data
sheet that comes with the products or the
T1K-INST-M
Installation
I/O
Manual
(available
www.automationdirect.com.) The technical
data sheet contains information that must
be followed. The system installation should
comply with all appropriate electrical codes
and standards.
Unit dimensions and
mounting orientation
Use the following diagrams to decide if
the Terminator I/O system can be installed
in your application. Terminator I/O units
should be mounted horizontally. To ensure
proper airflow for cooling purposes, units
should not be mounted upside-down. It
is important to check the Terminator I/O
dimensions against the conditions required
for your application. For example, it is
recommended to leave 2" depth for ease of
access and cable clearance. However, your
distance may be greater or less. Also, check
the installation guidelines for the recom-
mended cabinet clearances.
48mm
(1.89in)
80mm
(3.15in)
Power Supply
w w w . a u t o m a t i o n d i r e c t . c o m
and
online
at
Ambient Operating
Temperature
Storage
Temperature
Ambient Humidity
Atmosphere
Vibration
Resistance
Shock Resistance
Voltage Withstand
(Dielectric)
Insulation
Resistance
Noise Immunity
Agency Approvals
48mm
(1.89in)
80mm
(3.15in)
Network Interface Module
Half-size I/O Module
with Base
Terminator I/O Environmental Specifications
32°F to 131°F (0°C to 55°C)
-4°F to 158°F (-20°C to 70°C)
5% to 95% (Non-condensing)
No corrosive gases. The level of environmental
pollution = 2 (UL 840)
MIL STD 810C, Method 514.2
MIL STD 810C, Method 516.2
1500VAC, 1 minute
500 VDC, 10 Mq
NEMA ICS3-304
Impulse noise 1µs, 1000V
FCC class A
RFI (144MHz, 430MHz 10W, 10cm)
UL, CE, FCC class A, NEC Class 1 Division 2
48mm
(1.89in)
80mm
(3.15in)
Full-size I/O Module
For the latest prices, please check AutomationDirect.com.
See the Enclosures
section for an enclosure that may
be suitable for your application
89mm
(3.5in)
80mm
(3.15in)
with Base
Universal Field I/O
83.3mm
(3.28in)
System Depth
tFED-53