AutomationDirect IronHorse GSDA-DP-S Manuel de l'utilisateur - Page 12
Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} AutomationDirect IronHorse GSDA-DP-S. AutomationDirect IronHorse GSDA-DP-S 16 pages. Signal conditioner/generator
Parameter
98
Save to User Default Area
99
Restore from User Default Area
P
D
araMeter
escriPtiOns
Item
Parameter Name
0
Exit to Running Mode
1
Model Number
2
Software Build
3
Hardware Version
4
Serial Number - Major (Reserved)
5
Serial Number - Minor (Reserved)
10
Generate/Scale
11
Display Intensity
12
Display Zero Blanking
13
Decimal Point Position
15
Keypad Mode
Page 12
Description
0–Do Nothing and Exit
1–Save Settings
0–Do Nothing and Exit
1–Restore Settings
When parameter 0 is selected in Parameter-Selection Mode, the
unit will return to Running Mode and display the running value�
This should be selected once the changes to the parameters are
completed�
Read-Only Identification Items
This is a number which represents the base model number for the
product� The model code for the GSDA-DP-S is 90�
The software build is a code which identifies the software version
of the unit�
The hardware version is a code which identifies which hardware
was used to build the unit�
These parameters are reserved for future use as an electronic serial
number and are unique to each manufactured unit�
General Setup
Mode 1: Generate–Generate Output Signal
Mode 2: Scale–Scale Input Signal
This parameter adjusts the intensity of the LED display digits in
the front panel of the unit� The values of 0 – 31 correspond to a
gradual change from very dim to very bright�
This selects the number of display digits that are required to be
displayed regardless of the display value� For example, with a
Display Zero Blanking setting of 3 and a displayed value of 6, the
display would show "_006"�
• Mode 1: ___X
• Mode 2: __XX
• Mode 3: _XXX
• Mode 4: XXXX
This selects the format of the display with respect to the decimal
point's position� This parameter does not affect the value entry
for other parameters� For example, if the user desires to display
numbers such as 12�34 or 1�05, then parameter 13 should be set
to 2�
• Mode 0: Fixed XXXX (DP disabled)
• Mode 1: Fixed X�XXX
• Mode 2: Fixed XX�XX
• Mode 3: Fixed XXX�X
• Mode 4: Fixed XXXX�
This parameter selects the operating mode of the front-panel push
buttons� In some applications, increasing or decreasing the scroll
rate provides the user more controllability when entering settings�
Parameters 14 and 15 affect only the Up and Down buttons when
the user interface is in Running Mode�
• Mode 1: Linear, Constant Rate
In linear mode, pressing and holding the Up or Down buttons
will cause the display to continuously change value in the
requested direction until either the Display Minimum or Display
Maximum is reached� The displayed value will scroll at a
constant rate which is specified using parameter 16�
• Mode 2: Non-linear, Accelerating Rate
In non-linear mode, pressing and holding the Up or Down
buttons will cause the display to continuously change value in
the requested direction until either the Display Minimum or
Display Maximum is reached� The displayed value will initially
scroll at a slow rate and increase in speed until the maximum
scroll rate is achieved� The initial scroll rate is specified using
parameter 16�
IronHorse GSDA-DP-S User Manual – 1st Edition – 09/18/2019
Value Range
Units
Description
Always show at least 1 digit
Always show at least 2 digits
Always show at least 3 digits
Always show all 4 digits
Default
0