ADEMCO 5192CP Instructions d'installation et d'entretien - Page 2
Parcourez en ligne ou téléchargez le pdf Instructions d'installation et d'entretien pour {nom_de_la_catégorie} ADEMCO 5192CP. ADEMCO 5192CP 4 pages. Adressable ionization smoke detector

WIRING INSTALLATION
GUIDELINES
All Wiflng must be installed in Compfia"ce with the National Electrical Code, local codes, and any special req"ireme"ts of the a"thOri~
having jutisdition,
Proper wire gauges should be used. The co"ductor$ used tO connect the smoke detectOr~ tOthe control paneI and
accesso~ devices should be color-coded to reduce the Iikefihood of witing errors. Improper connections can prevent a system from
responding properly in the event of a fire.
The screw terminal block accepts 14 to 22 gauge wire. For best system petiormance,
all wifing should be installed in separate
grounded conduit. Do not mix fire system wiring in the same conduit as any other etecttical witing. Twisted pair or shielded cable may
be used to provide additional protection against electrical intetierence. If shielded cable is used, the shield connection to and from the
detector must be confinuoua by using wire nuts, ctimping, or soldeting aa appropriate for a refiabie connection.
Smoke detectors and slam system control panels have specifications for allowable loop resistance. Consult the control panel specifi-
=tions for the total loop resistance allowed for the control panel being used before witing the detector loops. Wire connections are
made by sttipping about 'It of insulation from the end of the feed wire, insetitng the wire into the appropriate terminal, and tightening
the screw to secure the wire in place,
NOTE Using Wisted, shielded wire will result in decre~ed
overall cable run as specified in the control installation instructions
INSTALLATION
Remove power from the control unit or initiating device circuits before instalhn.a detectors.
i.
2.
3.
4.
5.
6.
7.
Vtire the plug-in screw terminal block (see Figure 3) and plug the teminai-blxk
into the detetior.
Afign the arrows on the detector with the arrows on the mounting bracket.
Turn the detector cloc~se
in the mounting bracket until it chcks into place,
After all the detectors have been installed, apply power to the control unit or initiating device circuits
Test the detector as desctibed in TESTING,
Rest the detector at the system control panel.
Notify the proper authorities that the svstem is in ooeratio".
____i-
,-,
,7h___:.
O;~lONAL
CABLE SH!ELD
II
avvl
I UH
>REMO"ABLE
TERM,NALBL~
A78-,389.03
1
!
Rgure 3. Wring W"agram for 5192CP smoke deteaor
OETECTOR ID NO.
IMPORTANT
The 5t 92 smoke detector provides for both DIP switch and serial number addressing,
DIP swich postions 1-7 are
used
for setting the zone number with older controls which only suppoti DIP swfich addressing. The permissible DIP switch addresses
are from 10 to 63 as shown in Table 1, [f the5192 smoke detector is to be used with newer controls that suppofl setial number address-
ing, you MUST configure the detector as a setial number device duriilg the zone programming procedure for those controls. DIP switch
addressing of the 5192 with controls that suppon serial number addressing may result in polfing loop trouble conditions.
TESTING THE 5192CP SENSITIVITY
NOTE
Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily
out of sewice. Disable the zone or system undergoing maintenance to prevent unwanted alarms. Notify the proper authorities
that the system is back in operation when finished testing.
Detectors must be tested after installation and following petiodic maintenance. Both smoke and heat detection testing are recom-
mended for veri~ng system protection capabihfy Test the 5192CP as follows
A. Test Switch
1. Press and hold the recessed test switch, located on the detector housing (see Rgure 4), for 15 seconds with a 0.18 inch maximum
diameter tool such as an Allen wrench or small screwdriver.
AD400-t 9-00
2
156-I 001-03