Automationdirect.com AcuAMP ACTR Series Instructions d'installation

Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} Automationdirect.com AcuAMP ACTR Series. Automationdirect.com AcuAMP ACTR Series 2 pages.

Specifications
24VDC nominal, (12-32VDC)
Power Supply
Intended for use with a Class 2 source with the
secondary fused to limit power to a maximum
of 100 VA
Output Signal
4-20 mA, Loop Powered
Output Limit
23mA
Output Impedance
< 600Ω @ 24VDC
Accuracy
1.0% FS, 10 to 100% of range
ACT: 50/60Hz, Average Responding
Frequency Range
ACTR: 20-400Hz, True RMS
Isolation Voltage
UL tested to 2200VAC
Response Time
600ms (90% step change)
Case
UL 94V-0 Flammability rated thermoplastic
2.22 X 1.19 in (56.3 X 30.2 mm)
Sensing Aperture
ACT1200:
3.44 x 2.31 in (87.3 x 58.8 mm)
-Temp -4 to 122°F (-20 to 50°C)
-Humidity 0-95% RH, Non-condensing
Environmental
-Pollution degree 2
-Altitude 2000 meters
UL/cUL File E197592
Certifications
CE
Sensed Current Limit
Range
Continuous 6 Seconds
All
1600A
1920A
For products intended for the EU market, the
following is applicable to the CE compliance of
the product:
The ACT/ACTR Series may comply with EN 61010-1 CAT III
300V max line-to-neutral measurement category. If insulated
cable is used for the primary circuit, the voltage rating of the
measurement category can be improved according to the
characteristics given by the cable manufacturer.
ACT 400 - 42L - S
ACT: AC current transducer, average responding
ACTR: AC current transducer, True RMS
Warning! Risk of hazardous voltage
When operating the transducer, certain parts
may carry hazardous live voltage (e.g., primary
conductor, secondary terminals). The transducer
should not be put into service if the installation is
not complete.
Warning! Risk of electric shock or
personal injury
1 Second
Safe operation can only be guaranteed if the
transducer is used for the purpose for which it was
6400A
designed and within the limits of the technical
specifications. When this symbol is used, it
means you should consult all documentation to
understand the nature of potential hazards and
the action required to avoid them.
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
Part Number Key
CASE STYLE
S - Split Core
OUTPUT
42L - 4-20mA, loop powered
RANGE
400 A
600 A
800 A
1200 A
AutomationDirect.com (ADC)
ACT/ACTR - Inst - Rev 1
0820
P-N 292000109
ACT/ACTR
SERIES
INSTALLATION
INSTRUCTIONS
Quick Start Guide
1.
Remove top section of sensing ring off by
carefully prying clips away and lifting the
section vertically.
2. Mount the sensor to a DIN rail or surface
using screws in corners, if needed.
3. Place conductor inside ring and replace top
section until the clips snap firmly closed.
4. Connect output wiring.
a. Use No. 22 to 14 AWG copper wires rated
min. 75C and tighten terminals to 5-7 in-lbs.
b. Ensure output load does not exceed
product specifications.
c. Connect 24 VDC power supply and load
in series. Observe polarity.
5. Verify that the display or controller is
reading the output correctly (4mA)
6. Energize the monitored circuit.
®
.