Cables are routed to the terminal block via the cable cord grips at the rear of the unit and then through
the back of the electrics box (see page 2).
Cables MUST be size compatible with the recommended system fuse.
FUSES
CX(E)A30 + CKA35
CX(E)A50 + CKA35
CX(E)A50 + CKA50
CX(E)A70 + CKA70
Note: On 3 ph systems the supply must go to the CKA outdoor unit and then to the CX(E)A indoor unit.
MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit
weight. Leave space around the unit for air circulation and access for installation and maintenance.
1.
Individual pipe runs to a maximum of 15m, including 7.5m lift, are permissible.
Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will result in no
significant loss of capacity on extended pipe runs.
a) Pipe sizes are based on:-
Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.
Maximum of 15.2 m/s (3000 fpm) suction gas.
b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil
returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.
2.
In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into
account. The table below covers the fittings most likely to be encountered in this installation.
The equivalent lengths of all the fittings in a pipe run should be added together and the total added to
the actual pipe length in order to calculate the total equivalent length.
3.
Use the shortest possible route, avoiding sharp bends.
4.
Completely insulate the suction line, fully over the indoor unit drain tray.
CX(E)A ELECTRICAL CONNECTIONS
COOL ONLY
SYSTEM
1PH
16A
20A
20A
20A
CKA INSTALLATION
WITH ELECTRIC
HEATER
3PH
1PH
-
16A
-
20A
-
20A
-
32A
8/9
3PH
-
-
-
-