Functions
Alarm [ AL-1 / AL-2 ]
Alarm operation
Mode
Name
-
-
AM)_
Deviation
high-limit
AM!
alarm
Deviation
low-limit
AM@
alarm
Lower deviation: Set as 10℃ Lower deviation: Set as -10℃
Deviation
high/low-limit
AM#
alarm
Deviation
high/low-limit
AM$
reserve alarm
Absolute
value high
AM%
limit alarm
Absolute
value low
AM^
limit alarm
Sensor break Alarm -
SBa
Loop break Alarm
-
LBa
※ H: Alarm output hysteresis [ AHYS ]
Alarm option
Mode
Name
Standard alarm
AM .A
Alarm latch
AM .B
Standby sequence 1
AM .C
Alarm latch and
AM .D
standby sequence 1
Standby sequence 2
AM .E
Alarm latch and
AM .F
standby sequence 2
※ Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, changing set
temperature, alarm temperature [ AL1 , AL2 ] or alarm operation [ AL-1 , AL-2 ], switching STOP mode to RUN mode.
Sensor break alarm
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is detected during temperature
controlling. You can check whether the sensor is connected with buzzer or other units using alarm output contact. It is selectable between
standard alarm [ SBaA ], or alarm latch [ SBaB ].
AM!A
Alarm
Alarm
operation
option
Alarm operation
OFF
H
ON
OFF
SV
PV
100℃
110℃
High deviation: Set as 10℃
High deviation: Set as -10℃
ON
H
OFF
PV
SV
90℃
100℃
ON
H
OFF
PV
SV
90℃
100℃
High/Lower deviation: Set as 10℃
ON
H
OFF
PV
SV
90℃
100℃
High/Lower deviation: Set as 10℃
OFF
H
ON
PV
SV
90℃
100℃
Absolute-value Alarm:
Absolute-value Alarm:
Set as 90℃
ON
H
OFF
PV
SV
90℃
100℃
Absolute-value Alarm:
Absolute-value Alarm:
Set as 90℃
Description
If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON status. (Alarm output HOLD)
First alarm condition is ignored and from second alarm condition, standard alarm operates.
When power is supplied and it is an alarm condition, this first alarm condition is ignored and from the
second alarm condition, standard alarm operates.
If it is an alarm condition, it operates both alarm latch and standby sequence. When power is supplied
and it is an alarm condition, this first alarm condition is ignored and from the second alarm condition,
alarm latch operates.
First alarm condition is ignored and from second alarm condition, standard alarm operates.
When re-applied standby sequence and if it is alarm condition, alarm output does not turn ON.
After clearing alarm condition, standard alarm operates.
Basic operation is same as alarm latch and standby sequence 1. It operates not only by power ON/OFF,
but also alarm setting value, or alarm option changing. When re-applied standby sequence and if it is
alarm condition, alarm output does not turn ON.
After clearing alarm condition, alarm latch operates.
Economical PID Control
Set both alarm operation and alarm option by combining.
Each alarm operates individually in two alarm output models.
When the current temperature is out of alarm range, alarm clears
automatically. If alarm option is alarm latch or alarm latch and standby
sequence 1/2, press digital input key( +
key[DI-K] of Parameter group 2 set as AlRE), or turn OFF the power
and turn ON to clear alarm.
Description
No alarm output
H
ON
If deviation between PV and SV as high-limit is
higher than set value of deviation temperature,
PV
SV
90℃
100℃
the alarm output will be ON.
ON
H
OFF
If deviation between PV and SV as low-limit is
higher than set value of deviation temperature,
SV
PV
100℃
110℃
the alarm output will be ON.
H
ON
If deviation between PV and SV as high/low-limit
is higher than set value of deviation temperature,
PV
110℃
the alarm output will be ON.
H
ON
If deviation between PV and SV as high/low-limit
is higher than set value of deviation temperature,
PV
110℃
the alarm output will be OFF.
OFF
H
ON
If PV is higher than the absolute value,
SV
PV
the output will be ON.
100℃
110℃
Set as 110℃
ON
H
OFF
If PV is lower than the absolute value,
SV
PV
the output will be ON.
100℃
110℃
Set as 110℃
It will be ON when it detects sensor disconnection.
It will be ON when it detects loop break.
(A)
Photoelectric
Sensors
(B)
Fiber
3 sec., digital input
Optic
Sensors
(C)
Door/Area
Sensors
(D)
Proximity
Sensors
(E)
Pressure
Sensors
(F)
Rotary
Encoders
(G)
Connectors/
Sockets
(H)
Temperature
Controllers
(I)
SSRs / Power
Controllers
(J)
Counters
(K)
Timers
(L)
Panel
Meters
(M)
Tacho /
Speed / Pulse
Meters
(N)
Display
Units
(O)
Sensor
Controllers
(P)
Switching
Mode Power
Supplies
(Q)
Stepper Motors
& Drivers
& Controllers
(R)
Graphic/
Logic
Panels
(S)
Field
Network
Devices
(T)
Software
H-63