LE365S-41
• Set range for ON/OFF time width
: 1min to 12 hour 59min
• One record in 3 steps (ON day/ON time, OFF day/OFF
time, ON time width/OFF time width)
OFF width
ON Time
● Weekly pulse mode
Output turns ON at ON time for a specified pulse width.
(Pulse width: 1 to 59sec, 1 to 60min)
• One record in two steps (ON day/ON time, pulse width)
(1 to 59sec, 1 to 60min)
● Yearly ON/OFF mode
Output turns ON at ON time on START date and turns OFF
at OFF time on STOP date.
• One Record in three Steps (START/STOP date, ON/OFF
time)
● Yearly pulse mode
Output turns ON at ON time on START date and turns
OFF at OFF time on STOP time for a specified pulse width
repeatedly.
• One record in three steps (START/STOP date, ON time,
Pulse width)
Program operation
Weekly setting 1 of Program 1
Weekly setting 2 of Program
Yearly setting 1 of Program
Output operation
● ① to ②: Operated by weekly setting 1 of Program 1.
● ② to ③: Operated by weekly setting 2 of Program 1.
● ④ to ⑤: Operated by weekly setting 1 of Program 1.
● ⑤ to ⑥: Operated by yearly setting 1 of Program 1.
(during weekly program operation at 12:00 AM on START
date, the weekly program operation stops, and it changes
to yearly program operation mode. The yearly program
operation stops at 12:00 AM on the next day of STOP
date.)
Display and change of next mode
● The day of next mode in Program is displayed on the day
indicator, and the time of next mode is displayed on the
lower row of screen.
● In ON/OFF operation mode, set ON time and OFF time
to next mode. In Pulse operation mode, set Pulse ON
time to next mode.
K-92
ON width
OFF Time
Pulse width
ON time
1
1
①
② ③ ④ ⑤
Power restore mode
In setting group 2 - LEVEL2 ( RET turns ON, AT or NOR
flashes), select Auto[ AT ] or Normal [ NOR ] by
and press
key to set.
SET
● Auto [ AT ] power restore mode
Output operates according to program when power turns
ON again after power failure.
●Normal[ NOR ] power restore mode
When power turns ON again after power failure, output
is kept OFF and rIN flashes on the lower row of screen
and power restore input (press
RUN mode) is applied, rIN turns OFF and output
operates according to program.
Season switching mode
This feature uses for setting seasonal weekly operation
mode. To operate this mode, save starting month and date,
ending month and date of each season which displays S1,
S2, S3, S4 then set day and time of each season in weekly
program setting. It is also able to operate only in summer
and winter season. (S1: set summer season, S2: set winter
season, S3/S4: do not set)
In setting group 2-Level 2 ( SEN turns ON, OFF flashes.),
select ON[ ON ] by
When the season switching mode changed from OFF
to ON or vice versa, previous set programs are deleted.
● ON[ ON ] mode
Weekly program is switched automatically by season
switching.
• Period setting per season
① Press
key in period setting per season mode of
SET
setting group 2. ( SEN flashes, season with preset period
turns ON and START and STOP turn ON.)
② Advance to the flashing position of season selection
among S1, S2, S3, S4 by
key.
③ After set START month, date per season and press
key.
④
key is pressed after set STOP month, date per
SET
season, it is advanced to LEVEL1 of period setting per
season. Add or adjust the period setting by
● It is disable to use when it is OFF [ OFF ].
⑥
● If season terms are overlapped, these are prioritized in
S4>S3>S2>S1 order.
key over 3 secin
SET
or
key and press
key to save.
SET
or
key and press
SET
or
key
SET
SET
key.