Galaxy Control Systems 635 Series Feuille de travail - Page 5
Parcourez en ligne ou téléchargez le pdf Feuille de travail pour {nom_de_la_catégorie} Galaxy Control Systems 635 Series. Galaxy Control Systems 635 Series 5 pages. System galaxy installation worksheet
11.
Connect the reader wiring to the DRM board:
•
6-conductor, 22 AWG, overall shielded; max cable distance is 500 feet to the panel.
Ground the Drain-wire at one end only - at the DRM Board (GND).
•
•
Reader will require separate power supply if the current draw is over 150 mA
Refer to manufacturer's instructions for wiring (manufacturer's specs may supersede Galaxy specs).
•
Wiegand Reader
LED Control
DATA 1
VDC
GND
DATA 0
See System Galaxy Online Help
12.
Connect the Lock, Door Contacts, and REX to the DRM ...
Connection Type
Request to Exit
Door Contact
Lock Hardware
Refer to manufacturer's instructions for device wiring (manufacturer's specs may supersede Galaxy specs).
13.
Jumper-out unused contacts, as follows
DRM board: If Door Contacts are not installed, you must jumper-out CNT to GND.
a)
CPU board: If Low Battery wiring is not installed, you must jumper-out Low Batt to GND.
b)
CPU board: If AC Fail wiring is not installed, you must jumper-out the AC Fail to GND.
c)
14.
Now you are ready to add your Cluster and Controller information into the SG software programming screens.
The software can auto-import the daughter boards into the Controller programming screen by clicking the
•
[Get Boards] button, as long as they are physically attached to the CPU I2C-Data (ribbon cable).
You must manually program each Reader, Input, and Output into the SG programming screens and make
•
any schedules you need.
15.
Test that your Tamper Switch is working is working on each controller. The CPU reports tamper events to System
Galaxy software.
635-DRM Terminals (Function)
LED
(LED control line)
D 1
(Data 1)
VDC
(+12 VDC)
GND
(Power Supply Ground)
D 0
(Data 0)
Reader Wiring Guide
Max Distance
500 ft. from controller
500 ft. from controller
500 ft. from controller
*for +5VDC use Regulator PN 92-3001-05
for additional reader formats.
Wire Gauge & Specifications
22 AWG; 4-conductor, overall shielded; wired normally open (NO)
22 AWG; 2-conductor, overall shielded; wired normally closed (NC)
18 AWG; 2-conductor minimum, shielded; Separate Power Supply.
Page 5 of 5