Register
Coil /
Address
Discrete
Address
22
23
3
-
4
-
5
-
LSB
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
MSB
80
6
-
7
-
8
-
9
-
10
-
11
-
12
-
13
-
14
-
15
-
16
-
17
-
18
-
19
-
20
-
14
Read Only
Description
(RO) or
Read/Write
(RW)
RW
Disable Snore Stop.
RW
Disable (Pause) Timer Start.
-
Unused
-
Unused
RO
Discrete Status Values
RO
Low Float / Stop Input is active.
RO
High Float / Start Input is active.
RO
Pump Run Relay is On.
RO
Alarm Relay is On. (An alarm is active.)
RO
Remote Configuration Mode is active.
RO
Pump is Snoring.
RO
AIN 1 / CT Input is too high.
RO
AIN 1 / CT Input is too low.
RO
Pump has failed to run.
-
Unused
-
Unused
-
Unused
RO
Active Alarms
Alarm for Analog Input (CT Input) low is active.
RO
Alarm for Low Float Active.
RO
Alarm for High Float Active.
RO
Alarm for Pump Fails to Run. Pump Run Relay Active, but no current was detected.
-
Unused
-
Unused
-
Unused
RO
Pump Control State:
0: Initial State
1: Pump Pausing (waiting for Pause Timer to expire)
2: Pump Running
3: Low Level active (Pump Stopped)
4: High Level active (Pump Running)
5: Pump is pausing to flush pump.
6: Pump is starting (Pump not yet running.)
RO
Pump Current. Percentage with 1 decimal place. e.g. 125 = 12.5%
RO
Pump Stop Current (Snore Setpoint). . Percentage with 1 decimal place. E.g. 125 =
12.5%. Note: Read Only. See Register 23 for the actual setpoint.
The Duration of this pump run:
RO
Hours
RO
Minutes
RO
Seconds
RO
The Time remaining of the current Pause Timer:
Hours
RO
Minutes
RO
Seconds
Settings / Configuration (Remote Configuration Mode Only.)
IMPORTANT: To save changes to these settings, set coil 4 (see above).
RW
The Pump Run Time Target Setting:
... Hours
RW
... Minutes
RW
... Seconds